Disinfection of the water Tank and the Distribution System with Calcium Hypochlorite or Sodium Hypochlorite


TASK 38-10-00-670-003-A-01
Disinfection of the water Tank and the Distribution System with Calcium Hypochlorite or Sodium Hypochlorite


WARNING: ALWAYS WEAR RUBBER GLOVES, GOGGLES AND PROTECTIVE CLOTHES WHEN YOU DO THIS TASK.
WARNING: BE CAREFUL WHEN YOU USE CONSUMABLE MATERIALS. OBEY THE MATERIAL MANUFACTURER'S INSTRUCTIONS AND YOUR LOCAL REGULATIONS.
WARNING: REFER TO THE MANUFACTURER'S MATERIAL SAFETY DATA SHEETS FOR CONSUMABLE MATERIAL INFORMATION. THIS INCLUDES HAZARDOUS INGREDIENTS, PHYSICAL AND CHEMICAL CHARACTERISTICS, FIRE, EXPLOSION, REACTIVITY, HEALTH HAZARD DATA, PRECAUTIONS FOR SAFE HANDLING, AND USE OF CONTROL MEASURES.
NOTE: Airbus recommends to do an analysis of water sample before you do the disinfection procedure.
1. Reason for the Job
NOTE: There is an alternative method for this procedure. This task gives one of the methods. For the other method, refer to the other tasks in this page block.
2. Job Set-up Information
 A. Fixtures, Tools, Test and Support Equipment
REFERENCE
QTY
DESIGNATION
No specific
2
ACCESS PLATFORM 1M(3 FT)
No specific
1
CART - GROUND, NITROGEN
No specific
1
CART - SERVICING, WATER, POTABLE
No specific
1
CONTAINER 300 L(80 USGAL)
No specific
1
CONTAINER 5 L (1.32 USGAL)
No specific
AR
HOSE - VINYL
No specific
AR
SAFETY CLIP - CIRCUIT BREAKER
No specific
AR
WARNING NOTICE(S)
No specific
1
WATER SOURCE - GROUND
 B. Consumable Materials
REFERENCE
DESIGNATION
(Material No.11AKB1)
Disinfectant-Potable Water System Hypochlorite -
No specific
Test Strips for Free Chlorine
 C. Work Zones and Access Panels
ZONE/ACCESS
ZONE DESCRIPTION
133AL, 171AL
192NB
 D. Referenced Information
REFERENCE
DESIGNATION
TASK 12-15-38-613-001-A
Fill the Potable Water Tank System (Aircraft Electrical Power Available)
TASK 12-15-38-613-002-A
Fill the Potable Water Tank System (Aircraft Electrical Power not Available)
TASK 12-24-38-680-001-A
Draining of the Potable Water System (with Electrical Power)
TASK 12-24-38-680-002-A
Draining of the Potable Water System (without Electrical Power)
TASK 12-31-38-660-001-A
Cold Weather Maintenance - Water/Waste
TASK 12-33-21-618-001-A
Pre-conditioning through the LP Ground Connection (Aircraft Electrical Power Available)
TASK 12-33-21-618-001-A-01
Pre-conditioning through the HP Ground Connection
TASK 12-33-21-618-001-A-02
Pre-conditioning with the APU
TASK 12-33-21-618-001-A-03
Pre-conditioning through the LP Ground Connection (Aircraft Electrical Power Not Available)
TASK 24-42-00-861-001-A
Energize the Ground Service Network from the External Power
TASK 24-42-00-862-001-A
De-energize the Ground Service Network Supplied from the External Power
TASK 38-10-00-614-001-A
Pressurization of the Potable Water System from a Ground Air Supply
TASK 38-10-00-614-002-A
Depressurization of the Potable Water System
TASK 38-10-00-614-003-A
Pressurization of the Potable Water System with the Compressor
TASK 38-12-23-920-802-A
Replacement of the Galley Water-Filter Elements
TASK 38-12-41-000-006-A
Removal of the Nozzle Assembly
TASK 38-12-41-000-006-A-01
Removal of the Nozzle Assembly
TASK 38-12-41-400-006-A
Installation of the Nozzle Assembly
TASK 38-12-41-400-006-A-01
Installation of the Nozzle Assembly
TASK 25-35-00-00
GALLEY EQUIPMENT - DESCRIPTION AND OPERATION
3. Job Set-up
Subtask 38-10-00-861-069-A
A. Energize the ground service network
(Ref. AMM TASK 24-42-00-861-001).
Subtask 38-10-00-680-066-A
B. Drain the potable water system (Ref. AMM TASK 12-24-38-680-001) or (Ref. AMM TASK 12-24-38-680-002).
Subtask 38-10-00-560-089-A
C. Preparation of the Disinfectant Solution with Calcium Hypochlorite or Sodium Hypochlorite
WARNING: ALWAYS WEAR RUBBER GLOVES, GOGGLES AND PROTECTIVE CLOTHES WHEN YOU DO THIS TASK.
WARNING: DO NOT GET THE FLUID ON YOUR SKIN OR IN YOUR EYES. IF YOU DO:
  • FLUSH IT AWAY WITH CLEAN WATER
  • GET MEDICAL AID.
   (1) Prepare the dissolved solution:
     (a) Mix Disinfectant-Potable Water System Hypochlorite - (Material No.11AKB1) with water at a temperature of 20 +4 deg.C or -4 deg.C (68.00 +7.20 deg.F or -7.20 deg.F) in a CONTAINER 5 L (1.32 USGAL) as given in table 1 or table 2.
NOTE: Airbus recommends:
  • To use water from the cold water tap for the disinfection of the potable water system.
  • Not to keep water or disinfectant solution in a very cold or hot condition before you do the disinfection procedure.
NOTE: The mixtures given in table 1 and 2 are for a concentration of 100 parts per million for a volume of 250 l (66.04 USgal) of water.
A/C Type
Number of tanks
Usable tank volume in l (USgal)
Water volume necessary for disinfection solution in l (USgal) *
Calcium hypochlorite (70%) (CML 14 003E) in g (ounces)
Sodium hypochlorite (13%) (CML 14 003F) in l (Usgal)
A318,A319
A320,A321
1
200 (53)
250 (66)
-
0.16 (0.04)
or
A/C Type
Number of tanks
Usable tank volume in l (USgal)
Water volume necessary for disinfection solution in l (USgal) *
Calcium hypochlorite (70%) (CML 14 003E) in g (ounces)
Sodium hypochlorite (13%) (CML 14 003F) in l (Usgal)
A318,A319
A320,A321
1
200 (53)
250 (66)
36 (1.3)
-
NOTE: The percent values of the mixtures given in table 1 and 2 are the concentration of free available chlorine.
NOTE: Table 1 and 2 give information only for the materials used in table 1 and 2. If the operator uses other disinfectant materials, it is necessary to obey the instructions from the manufacturer of those materials.

   (2) If you think that there is a large amount of contamination in the potable water system:
     (a) Let the disinfection solution flow longer through the water faucets in the lavatories and the galleys:
  • This is to make sure that the potable water system is clean.
   (3) Prepare the disinfectant solution:
     (a) Mix the dissolved solution with 250 l (66.04 USgal) of water in a CONTAINER 300 L(80 USGAL) to make the disinfectant solution (referred to as the solution).
Subtask 38-10-00-618-060-A
D. Preparation for Cold Weather Conditions
   (1) Obey the cold-weather maintenance procedure (Ref. AMM TASK 12-31-38-660-001).
   (2) If the temperature in the aircraft is below 4 DEG.C (39.20 DEG.F), do the pre-conditioning procedure (Ref. AMM TASK 12-33-21-618-001).
Subtask 38-10-00-865-094-A
E. Open, safety and tag this(these) circuit breaker(s):
PANELDESIGNATIONFINLOCATION
** ON A/C NOT FOR ALL
2000VULAV FWD & MID-HOT WATER-A1MBF02
** ON A/C NOT FOR ALL
2000VUWATER SYSTEM-DEPRESS1MDB02
2000VUWATER SYSTEM-QANT-IND1MAB01
** ON A/C NOT FOR ALL
2000VULAV FWD-HOT WATER-A1MBF02
** ON A/C NOT FOR ALL
2001VUVACU TOIL SYS-VACUUM-SYS35MGA06
2001VUWATER-SYSTEM-DEPRESS1MDF03
** ON A/C NOT FOR ALL
2001VUWATER SYS-QUANT-IND1MAB06
** ON A/C NOT FOR ALL
2001VUWATER SYS-AIR-COMPRESSOR19MDF01
** ON A/C NOT FOR ALL
2001VULAVATORY AFT-HOT WATER-D2MBB02
** ON A/C NOT FOR ALL
2001VUWATER SYS-DRAIN1MPB05
** ON A/C NOT FOR ALL
2001VUVACU TOIL SYS-VACUUM-GEN33MGA08
** ON A/C NOT FOR ALL
2001VUVACU TOIL SYS-LAV PWR-E34MGA04
** ON A/C NOT FOR ALL
2001VUVACU TOIL SYS-LAV PWR-D39MGA03
** ON A/C NOT FOR ALL
2001VULAV AFT-HOT WATER-E9MBB03
** ON A/C ALL
2001VUVACU TOIL SYS-LAV PWR-A32MGA01
** ON A/C NOT FOR ALL
2001VUVACU TOIL SYS-VACU-SYS35MGA06
** ON A/C NOT FOR ALL
2001VUWATER-SYS-DRAIN1MPB05
** ON A/C NOT FOR ALL
2001VULAV AFT-HOT WATER-D2MBB02
** ON A/C NOT FOR ALL
2001VUVACU TOIL SYS-VACU-GEN33MGA08
** ON A/C NOT FOR ALL
2001VULAV AFT-HOT WATER-G9MBB03
2001VULAV AFT-HOT WATER-D/F2MBB02
** ON A/C NOT FOR ALL
2001VUVACU TOIL SYS-LAV PWR-G34MGA04
2001VUVACU TOIL SYS-LAV PWR-F39MGA03
2001VUVACU TOIL SYS-LAV PWR-D45MGA02
** ON A/C NOT FOR ALL
2001VUWATER-SYSTEM-DEPRESS1MDD05
** ON A/C NOT FOR ALL
2001VULAV AFT-HOT WATER9MBB03
2001VULAV AFT-HOT WATER2MBB02
** ON A/C NOT FOR ALL
2001VULAV AFT-HOT WATER-E/L9MBB03
** ON A/C NOT FOR ALL
2001VUVACU TOIL SYS-LAV PWR-L45MGA02
** ON A/C NOT FOR ALL
2001VUVACU TOIL SYS-LAV PWR-L23MGA05
2001VULAV AFT-HOT WATER-L9MBC04
** ON A/C NOT FOR ALL
2001VULAV AFT-HOT WATER-D/L2MBB02
** ON A/C NOT FOR ALL
2001VUVACU TOIL SYS-LAV PWR-M34MGA04
2001VULAV AFT-HOT WATER-M9MBB03
Subtask 38-10-00-010-071-A ** ON A/C NOT FOR ALL
F. Get Access
   (1) Put an ACCESS PLATFORM 1M(3 FT) in position at zone 133.
   (2) Put an ACCESS PLATFORM 1M(3 FT) in position at zone 171.
   (3) Open service door 171AL and drain panel door 133AL.
   (4) Connect a HOSE - VINYL to the drain connections at the potable-water drain panels.
Subtask 38-10-00-010-071-B ** ON A/C NOT FOR ALL
F. Get Access
   (1) Put an ACCESS PLATFORM 1M(3 FT) in position at zone 133.
   (2) Put an ACCESS PLATFORM 1M(3 FT) in position at zone 171.
   (3) Open service door 171AL and drain panel doors 133AL and 192NB.
   (4) Connect a HOSE - VINYL to the drain connections at the potable-water drain panels.
Subtask 38-10-00-860-063-A ** ON A/C NOT FOR ALL
G. Aircraft Maintenance Configuration
WARNING: MAKE SURE THAT THE EQUIPMENT YOU USE FOR THIS PROCEDURE IS CLEAN AND APPROVED FOR THE POTABLE WATER SYSTEM. IF NOT IT CAN CAUSE CONTAMINATION OF THE POTABLE WATER SYSTEM.
   (1) Make sure that all the shutoff valves in the lavatories and the galleys are closed.
   (2) Make sure that the switch on each water heater is set to the OFF position.
   (3) Make sure that the water faucets in the lavatories and the galleys are in the middle (mixed) position.
   (4) Remove the water-faucet nozzle assemblies from the lavatories (Ref. AMM TASK 38-12-41-000-006).
   (5) Remove the equipment connected to the potable water system from each wet galley:
     (a) Find all the equipment connected to the potable water system (Ref. AMM D/O 25-35-00-00).
     (b) Remove the equipment you find. Refer to the related removal tasks for these components.
     (c) If the supplier of the equipment recommends to clean and disinfect the components, send them to the workshop.
   (6) Connect the HOSE - VINYL to the waste-water drain masts.
   (7) Connect a CART - SERVICING, WATER, POTABLE or a WATER SOURCE - GROUND to the fill/drain line of the Potable Water Service Panel (PWSP).
   (8) Connect a CART - GROUND, NITROGEN to the ground air connection on the PWSP.
Subtask 38-10-00-860-063-B ** ON A/C NOT FOR ALL
G. Aircraft Maintenance Configuration
WARNING: MAKE SURE THAT THE EQUIPMENT YOU USE FOR THIS PROCEDURE IS CLEAN AND APPROVED FOR THE POTABLE WATER SYSTEM. IF NOT IT CAN CAUSE CONTAMINATION OF THE POTABLE WATER SYSTEM.
   (1) Make sure that all the shutoff valves in the lavatories and the galleys are closed.
   (2) Make sure that the switch on each water heater is set to the OFF position.
   (3) Remove the water-faucet nozzle assemblies from the lavatories (Ref. AMM TASK 38-12-41-000-006).
   (4) Remove the equipment connected to the potable water system from each wet galley:
     (a) Find all the equipment connected to the potable water system (Ref. AMM D/O 25-35-00-00).
     (b) Remove the equipment you find. Refer to the related removal tasks for these components.
     (c) If the supplier of the equipment recommends to clean and disinfect the components, send them to the workshop.
   (5) Connect the HOSE - VINYL to the waste-water drain masts.
   (6) Connect a CART - SERVICING, WATER, POTABLE or a WATER SOURCE - GROUND to the fill/drain line of the Potable Water Service Panel (PWSP).
   (7) Connect a CART - GROUND, NITROGEN to the ground air connection on the PWSP.
Subtask 38-10-00-560-091-A
H. Preparation of the Water Filters
WARNING: WHEN YOU DO THIS WORK, ALWAYS PUT ON PROTECTIVE GLOVES, GOGGLES AND PROTECTIVE CLOTHING TO PREVENT INJURY.
   (1) Remove the galley water-filter elements (Ref. AMM TASK 38-12-23-920-802):
     (a) If the galley filter housings are installed, remove the caps and the filter elements:
  • Do not install the new filter elements at this time.
     (b) If the galley filter housings are removed, install the caps and tighten the clamps.
     (c) If the interface is installed, remove the canister:
  • Do not install a new canister at this time.
     (d) Install the bypass connector to the interface and tighten it.
NOTE: The bypass connector is attached to the interface.
Subtask 38-10-00-941-067-A
I. Safety Precaution
   (1) Put the WARNING NOTICE(S) in position to tell persons not to use the potable water system.
4. Procedure
Subtask 38-10-00-670-085-A ** ON A/C NOT FOR ALL
A. Disinfection of the Potable Water Tank and Distribution System
WARNING: DO NOT GET THE WATER WITH THE DISINFECTANT SOLUTION ON YOUR SKIN OR IN YOUR EYES. DO NOT LET WATER TOUCH SURFACES OTHER THAN THE WASH BASIN (WHEN THE NOZZLE ASSY IS NOT ON THE FAUCET, THE SOLUTION FLOWS OUT HORIZONTALLY). TO DO THIS: - PUT ON PROTECTIVE CLOTHING
  • PUT ON EYE PROTECTION OR GOGGLES
  • PUT A GUARD AROUND THE WATER FAUCET OUTLET TO CAUSE SPRAY FROM THE SOLUTION TO FLOW INTO THE WASH BASIN (SPRAY FROM THE SOLUTION MUST NOT GO ON ADJACENT SURFACES).
   (1) Depressurization of the potable water system:
     (a) Before you fill the potable water system, make sure that you do the depressurization of the potable water system (Ref. AMM TASK 38-10-00-614-002).
NOTE: After the depressurization of the potable water system, the solution can flow out of the POTABLE WATER OVERFLOW port when the potable water tank is filled.
   (2) On the PWSP:
     (a) Turn the FILL OVERFLOW DRAIN handle from the NORMAL to the FILL position.
     (b) Pull the FILL OVERFLOW DRAIN handle out to the mechanical stop.
   (3) Fill the potable water system with the solution.
   (4) Fill the potable water tank with water until the solution flows out of the POTABLE WATER OVERFLOW port (Ref. AMM TASK 12-15-38-613-001) or (Ref. AMM TASK 12-15-38-613-002).
   (5) On the PWSP:
     (a) Push the FILL OVERFLOW DRAIN handle in.
     (b) Turn the FILL OVERFLOW DRAIN handle from the FILL to the NORMAL position.
Subtask 38-10-00-670-085-B ** ON A/C NOT FOR ALL
A. Disinfection of the Potable Water Tank and Distribution System
WARNING: DO NOT GET THE WATER WITH THE DISINFECTANT SOLUTION ON YOUR SKIN OR IN YOUR EYES. DO NOT LET WATER TOUCH SURFACES OTHER THAN THE WASH BASIN (WHEN THE NOZZLE ASSY IS NOT ON THE FAUCET, THE SOLUTION FLOWS OUT HORIZONTALLY). TO DO THIS: - PUT ON PROTECTIVE CLOTHING
  • PUT ON EYE PROTECTION OR GOGGLES
  • PUT A GUARD AROUND THE WATER FAUCET OUTLET TO CAUSE SPRAY FROM THE SOLUTION TO FLOW INTO THE WASH BASIN (SPRAY FROM THE SOLUTION MUST NOT GO ON ADJACENT SURFACES).
   (1) Depressurization of the potable water system:
     (a) Before you fill the potable water system, make sure that you do the depressurization of the potable water system (Ref. AMM TASK 38-10-00-614-002).
NOTE: After the depressurization of the potable water system, the solution can flow out of the POTABLE WATER OVERFLOW port when the potable water tank is filled.
   (2) On the PWSP:
     (a) Turn the FILL/DRAIN handle from the NORMAL to the FILL position.
     (b) Pull the FILL/DRAIN handle out to the mechanical stop.
   (3) Turn the TANK OVERFLOW handle at panel 192NB from the CLOSE to the OPEN position.
   (4) Fill the potable water system with the solution.
   (5) Fill the potable water tank with water until the solution flows out of the POTABLE WATER OVERFLOW port (Ref. AMM TASK 12-15-38-613-001) or (Ref. AMM TASK 12-15-38-613-002).
   (6) Turn the TANK OVERFLOW handle from the OPEN to the CLOSE position.
   (7) On the PWSP:
     (a) Push the FILL/DRAIN handle in.
     (b) Turn the FILL/DRAIN handle from the FILL to the NORMAL position.
Subtask 38-10-00-865-095-A
B. Remove the safety clip(s) and the tag(s) and close this(these) circuit breaker(s):
PANELDESIGNATIONFINLOCATION
** ON A/C NOT FOR ALL
2001VUVACU TOIL SYS-LAV PWR-E34MGA04
** ON A/C NOT FOR ALL
2001VUVACU TOIL SYS-LAV PWR-D39MGA03
** ON A/C ALL
2001VUVACU TOIL SYS-LAV PWR-A32MGA01
** ON A/C NOT FOR ALL
2001VUVACU TOIL SYS-LAV PWR-G34MGA04
2001VUVACU TOIL SYS-LAV PWR-F39MGA03
2001VUVACU TOIL SYS-LAV PWR-D45MGA02
** ON A/C NOT FOR ALL
2001VUVACU TOIL SYS-LAV PWR-L45MGA02
** ON A/C NOT FOR ALL
2001VUVACU TOIL SYS-LAV PWR-L23MGA05
** ON A/C NOT FOR ALL
2001VUVACU TOIL SYS-LAV PWR-M34MGA04
Subtask 38-10-00-670-086-A ** ON A/C NOT FOR ALL
C. Disinfection of the Potable-Water Distribution System
WARNING: DO NOT GET THE WATER WITH THE DISINFECTANT SOLUTION ON YOUR SKIN OR IN YOUR EYES. DO NOT LET WATER TOUCH SURFACES OTHER THAN THE WASH BASIN (WHEN THE NOZZLE ASSY IS NOT ON THE FAUCET, THE SOLUTION FLOWS OUT HORIZONTALLY). TO DO THIS: - PUT ON PROTECTIVE CLOTHING
  • PUT ON EYE PROTECTION OR GOGGLES
  • PUT A GUARD AROUND THE WATER FAUCET OUTLET TO CAUSE SPRAY FROM THE SOLUTION TO FLOW INTO THE WASH BASIN (SPRAY FROM THE SOLUTION MUST NOT GO ON ADJACENT SURFACES).
   (1) Open all the manual shutoff valves in the lavatories and the galleys.
   (2) Do the pressurization of the potable water system (Ref. AMM TASK 38-10-00-614-001) or (Ref. AMM TASK 38-10-00-614-003).
   (3) Make sure that all the lines and equipment of the potable water system are filled with the disinfectant solution.
   (4) Bleed the potable water system:
     (a) In each lavatory, flush the toilet 15 times.
     (b) In each lavatory, operate the water faucet for 3 minutes.
     (c) In each galley, operate the water faucets at the sinks for 3 minutes.
     (d) Close all the potable-water shutoff valves (this lets the disinfection solution soak the two surfaces of the shutoff valves) and open all the shutoff valves again.
   (5) Do the depressurization of the potable water system (Ref. AMM TASK 38-10-00-614-002).
NOTE: After the depressurization of the potable water system, the solution can flow out of the POTABLE-WATER OVERFLOW port when the potable water tank is filled.
   (6) On the PWSP:
     (a) Turn the FILL OVERFLOW DRAIN handle from the NORMAL to the FILL position.
     (b) Pull the FILL OVERFLOW DRAIN handle out to the mechanical stop.
   (7) Fill the potable water system with the solution.
   (8) Fill the potable water tank with water until the solution flows out of the POTABLE WATER OVERFLOW port (Ref. AMM TASK 12-15-38-613-001) or (Ref. AMM TASK 12-15-38-613-002).
   (9) On the PWSP:
     (a) Push the FILL OVERFLOW DRAIN handle in.
     (b) Turn the FILL OVERFLOW DRAIN handle from the FILL to the NORMAL position.
   (10) Let the solution stay in the system for 1 hour.
   (11) Do the steps C.(1) thru C.(9) again and let the solution stay in the system for 0.5 hours more.
   (12) Disconnect the CART - SERVICING, WATER, POTABLE or the WATER SOURCE - GROUND.
   (13) Drain the potable water system (Ref. AMM TASK 12-24-38-680-001) or (Ref. AMM TASK 12-24-38-680-002).
Subtask 38-10-00-670-086-B ** ON A/C NOT FOR ALL
C. Disinfection of the Potable-Water Distribution System
WARNING: DO NOT GET THE WATER WITH THE DISINFECTANT SOLUTION ON YOUR SKIN OR IN YOUR EYES. DO NOT LET WATER TOUCH SURFACES OTHER THAN THE WASH BASIN (WHEN THE NOZZLE ASSY IS NOT ON THE FAUCET, THE SOLUTION FLOWS OUT HORIZONTALLY). TO DO THIS: - PUT ON PROTECTIVE CLOTHING
  • PUT ON EYE PROTECTION OR GOGGLES
  • PUT A GUARD AROUND THE WATER FAUCET OUTLET TO CAUSE SPRAY FROM THE SOLUTION TO FLOW INTO THE WASH BASIN (SPRAY FROM THE SOLUTION MUST NOT GO ON ADJACENT SURFACES).
   (1) Open all the manual shutoff valves in the lavatories and the galleys.
   (2) Do the pressurization of the potable water system (Ref. AMM TASK 38-10-00-614-001) or (Ref. AMM D/O 38-10-00-61).
   (3) Make sure that all the lines and equipment of the potable water system are filled with the disinfectant solution.
   (4) Bleed the potable water system:
     (a) In each lavatory, flush the toilet 15 times.
     (b) In each lavatory, operate the water faucet for 3 minutes.
     (c) In each galley, operate the water faucets at the sinks for 3 minutes.
     (d) Close all the potable-water shutoff valves (this lets the disinfection solution soak the two surfaces of the shutoff valves) and open all the shutoff valves again.
   (5) Do the depressurization of the potable water system (Ref. AMM TASK 38-10-00-614-002).
NOTE: After the depressurization of the potable water system, the solution can flow out of the POTABLE-WATER OVERFLOW port when the potable water tank is filled.
   (6) On the PWSP:
     (a) Turn the FILL/DRAIN handle from the NORMAL to the FILL position.
     (b) Pull the FILL/DRAIN handle out to the mechanical stop.
   (7) Turn the TANK OVERFLOW handle at panel 192NB from the CLOSE to the OPEN position.
   (8) Fill the potable water system with the solution.
   (9) Fill the potable water tank with water until the solution flows out of the POTABLE WATER OVERFLOW port (Ref. AMM TASK 12-15-38-613-001) or (Ref. AMM TASK 12-15-38-613-002).
   (10) Turn the TANK OVERFLOW handle from the OPEN to the CLOSE position.
   (11) On the PWSP:
     (a) Push the FILL/DRAIN handle in.
     (b) Turn the FILL/DRAIN handle from the FILL to the NORMAL position.
   (12) Let the solution stay in the system for 1 hour.
   (13) Do the steps C.(1) thru C.(9) again and let the solution stay in the system for 0.5 hours more.
   (14) Disconnect the CART - SERVICING, WATER, POTABLE or the WATER SOURCE - GROUND.
   (15) Drain the potable water system (Ref. AMM TASK 12-24-38-680-001) or (Ref. AMM TASK 12-24-38-680-002).
Subtask 38-10-00-170-064-A
D. Flush the Potable Water System (After Disinfection with Calcium Hypochlorite or Sodium Hypochlorite)
WARNING: DO NOT GET THE WATER WITH THE DISINFECTANT SOLUTION ON YOUR SKIN OR IN YOUR EYES. DO NOT LET WATER TOUCH SURFACES OTHER THAN THE WASH BASIN (WHEN THE NOZZLE ASSY IS NOT ON THE FAUCET, THE SOLUTION FLOWS OUT HORIZONTALLY). TO DO THIS: - PUT ON PROTECTIVE CLOTHING
  • PUT ON EYE PROTECTION OR GOGGLES
  • PUT A GUARD AROUND THE WATER FAUCET OUTLET TO CAUSE SPRAY FROM THE SOLUTION TO FLOW INTO THE WASH BASIN (SPRAY FROM THE SOLUTION MUST NOT GO ON ADJACENT SURFACES).
   (1) Drain the potable water system (Ref. AMM TASK 12-24-38-680-001) or (Ref. AMM TASK 12-24-38-680-002).
   (2) Fill the potable water system with clean water (Ref. AMM TASK 12-15-38-613-001) or (Ref. AMM TASK 12-15-38-613-002).
   (3) Do the pressurization of the potable water system (Ref. AMM TASK 38-10-00-614-001) or (Ref. AMM TASK 38-10-00-614-003).
   (4) Operate the water faucets in the lavatories and the galleys to flush them:
     (a) In the lavatories:
       1 Set the water faucet to the COLD position and fill the washbasin with water to the overflow level (approximately 3 l (0.79 USgal)).
       2 Drain the washbasin fully.
       3 Set the water faucet to the HOT position and fill the washbasin with water to the overflow level (approximately 3 l (0.79 USgal)).
       4 Drain the washbasin fully.
       5 Flush each toilet 15 times.
     (b) In the galleys, operate the water faucets at the sink.
Subtask 38-10-00-670-088-A
E. Test for Remaining Disinfectant
   (1) Examine the potable water in each galley and lavatory for the remaining disinfectant.
   (2) Do the test with Test Strips for Free Chlorine:
     (a) Carefully let the water flow on the test strip at the water faucets in the galleys and the lavatories.
   (3) If the test shows that there is remaining disinfectant in the water, that is more than the legal limit, flush the system again.
NOTE: These limits are given by the national health authority for drinking water.

5. Close-up
Subtask 38-10-00-560-092-A
A. Installation of the Filter Elements and the Nozzle Assemblies (After Disinfection of the Potable Water System with Calcium Hypochlorite or Sodium Hypochlorite)
   (1) Stop the ground air supply.
   (2) Install the galley water-filter elements (Ref. AMM TASK 38-12-23-920-802):
     (a) If the related galley filter housings are removed, install the new filter elements.
     (b) If the related interfaces are installed, remove the bypass connectors.
     (c) If the related interfaces are removed, install the new canisters.
     (d) Do a check for leaks:
       1 Make sure that there are no leaks.
   (3) Install the water-faucet nozzle assemblies (Ref. AMM TASK 38-12-41-400-006).
Subtask 38-10-00-865-096-A
B. Remove the safety clip(s) and the tag(s) and close this(these) circuit breaker(s):
PANELDESIGNATIONFINLOCATION
** ON A/C NOT FOR ALL
2000VULAV FWD & MID-HOT WATER-A1MBF02
** ON A/C NOT FOR ALL
2000VUWATER SYSTEM-DEPRESS1MDB02
2000VUWATER SYSTEM-QANT-IND1MAB01
** ON A/C NOT FOR ALL
2000VULAV FWD-HOT WATER-A1MBF02
** ON A/C NOT FOR ALL
2001VUVACU TOIL SYS-VACUUM-SYS35MGA06
2001VUWATER-SYSTEM-DEPRESS1MDF03
** ON A/C NOT FOR ALL
2001VUWATER SYS-QUANT-IND1MAB06
** ON A/C NOT FOR ALL
2001VUWATER SYS-AIR-COMPRESSOR19MDF01
** ON A/C NOT FOR ALL
2001VULAVATORY AFT-HOT WATER-D2MBB02
** ON A/C NOT FOR ALL
2001VUWATER SYS-DRAIN1MPB05
** ON A/C NOT FOR ALL
2001VUVACU TOIL SYS-VACUUM-GEN33MGA08
** ON A/C NOT FOR ALL
2001VULAV AFT-HOT WATER-E9MBB03
** ON A/C NOT FOR ALL
2001VUVACU TOIL SYS-VACU-SYS35MGA06
** ON A/C NOT FOR ALL
2001VUWATER-SYS-DRAIN1MPB05
** ON A/C NOT FOR ALL
2001VULAV AFT-HOT WATER-D2MBB02
** ON A/C NOT FOR ALL
2001VUVACU TOIL SYS-VACU-GEN33MGA08
** ON A/C NOT FOR ALL
2001VULAV AFT-HOT WATER-G9MBB03
2001VULAV AFT-HOT WATER-D/F2MBB02
** ON A/C NOT FOR ALL
2001VUWATER-SYSTEM-DEPRESS1MDD05
** ON A/C NOT FOR ALL
2001VULAV AFT-HOT WATER9MBB03
2001VULAV AFT-HOT WATER2MBB02
** ON A/C NOT FOR ALL
2001VULAV AFT-HOT WATER-E/L9MBB03
** ON A/C NOT FOR ALL
2001VULAV AFT-HOT WATER-L9MBC04
** ON A/C NOT FOR ALL
2001VULAV AFT-HOT WATER-D/L2MBB02
** ON A/C NOT FOR ALL
2001VULAV AFT-HOT WATER-M9MBB03
Subtask 38-10-00-613-072-A
C. Filling of the Potable Water System
   (1) If necessary, fill the potable water system (Ref. AMM TASK 12-15-38-613-001) or (Ref. AMM TASK 12-15-38-613-002).
Subtask 38-10-00-410-076-A ** ON A/C NOT FOR ALL
D. Close Access
   (1) Disconnect the ground air-supply cart.
   (2) Disconnect the hoses from the waste-water drain mast and the potable-water drain connection.
   (3) In each wet galley:
     (a) Install all equipment connected to the potable water system, which you removed for cleaning in the shop. Refer to the related installation tasks for these components.
   (4) Make sure that the work area is clean and clear of tools and other items.
   (5) Make sure that the manual shutoff valve of the potable water system is open.
   (6) Make sure that the switches on the water heaters in the lavatories are set to the ON position.
   (7) Close service door 171AL and drain panel door 133AL.
   (8) Remove the WARNING NOTICE(S).
   (9) Remove the access platform(s).
Subtask 38-10-00-410-076-B ** ON A/C NOT FOR ALL
D. Close Access
   (1) Disconnect the ground air-supply cart.
   (2) Disconnect the hoses from the waste-water drain mast and the potable-water drain connections.
   (3) In each wet galley:
     (a) Install all equipment connected to the potable water system, which you removed for cleaning in the shop. Refer to the related installation tasks for these components.
   (4) Make sure that the work area is clean and clear of tools and other items.
   (5) Make sure that the manual shutoff valve of the potable water system is open.
   (6) Make sure that the switches on the water heaters in the lavatories are set to the ON position.
   (7) Close drain panel doors 133AL and 192NB and service door 171AL.
   (8) Remove the WARNING NOTICE(S).
   (9) Remove the access platform(s).
Subtask 38-10-00-942-065-A
E. Remove the ground support and maintenance equipment, the special and standard tools and all other items.
   (1) To discard the used disinfection solution, refer to the national or local authority regulations.
Subtask 38-10-00-862-065-A
F. De-energize the ground service network
(Ref. AMM TASK 24-42-00-862-001).