Functional Test of the Cockpit and Cabin Temperature Control without CFDS/MCDU.
1. Reason for the Job
Self explanatory
2. Job Set-up Information
A. Referenced Information
| REFERENCE | DESIGNATION |
|---|---|
| TASK 12-33-21-618-001-A-01 | Pre-conditioning through the HP Ground Connection |
| TASK 12-33-21-618-001-A-02 | Pre-conditioning with the APU |
| TASK 24-41-00-861-002-A | Energize the Aircraft Electrical Circuits from the External Power |
| TASK 24-41-00-861-002-A-01 | Energize the Aircraft Electrical Circuits from the APU |
| TASK 24-41-00-861-002-A-02 | Energize the Aircraft Electrical Circuits from Engine 1(2) |
| TASK 24-41-00-862-002-A | De-energize the Aircraft Electrical Circuits Supplied from the External Power |
| TASK 24-41-00-862-002-A-01 | De-energize the Aircraft Electrical Circuits Supplied from the APU |
| TASK 24-41-00-862-002-A-02 | De-energize the Aircraft Electrical Circuits Supplied from the Engine 1(2) |
| TASK 31-60-00-860-001-A | EIS Start Procedure |
| TASK 31-60-00-860-002-A | EIS Stop Procedure |
Subtask 21-63-00-861-062-A Subtask 21-63-00-865-063-A
B. Make sure that this(these) circuit breaker(s) is(are) closed:
Subtask 21-63-00-860-054-A ** ON A/C NOT FOR ALL | PANEL | DESIGNATION | FIN | LOCATION |
|---|---|---|---|
| ** ON A/C NOT FOR ALL | |||
| 49VU | AIR COND/FLOW/CTL &/IND1 | 1HB | D07 |
| ** ON A/C NOT FOR ALL | |||
| 49VU | AIR COND/TEMP CTL/SYS 1 CHAN B/28VDC | 52HH | D08 |
| ** ON A/C NOT FOR ALL | |||
| 122VU | AIR COND/FLOW/MIXER/FLAP | 3HB | V22 |
| 122VU | AIR COND/FLOW/CTL AND IND/2 | 2HB | V21 |
| 122VU | AIR COND/ZONE TEMP CTL/28VDC/SYS2 | 4HK | V20 |
| 122VU | AIR COND/ZONE TEMP CTL/28VDC/SYS1 | 3HK | V19 |
| 122VU | AIR COND/ZONE TEMP CTL/115VAC/SYS2 | 2HK | V18 |
| 122VU | AIR COND/ZONE TEMP CTL/115VAC/SYS1 | 1HK | V17 |
| 122VU | AIR COND/PACK TEMP/CTL SYS1/2/115VAC | 21HH | W22 |
| 122VU | AIR COND/PACK TEMP/CTL SYS1/2/28VDC | 23HH | W21 |
| 122VU | AIR COND/PACK TEMP/CTL SYS1/1/115VAC | 1HH | X22 |
| 122VU | AIR COND/PACK TEMP/CTL SYS1/1/28VDC | 3HH | X21 |
| 122VU | AIR COND/PACK TEMP CTL SYS2/2/28VDC | 24HH | Y21 |
| 122VU | AIR COND/PACK TEMP CTL SYS2/2/115VAC | 22HH | Y20 |
| 122VU | AIR COND/PACK TEMP CTL SYS2/1/28VDC | 4HH | Y19 |
| 122VU | AIR COND/PACK TEMP CTL SYS2/1/115VAC | 2HH | Y18 |
| ** ON A/C NOT FOR ALL | |||
| 122VU | AIR COND/TEMP CTL SYS 2/CHAN A/115VAC | 53HH | W22 |
| 122VU | AIR COND/TEMP CTL SYS 2/CHAN A/28VDC | 55HH | W21 |
| 122VU | AIR COND/TEMP CTL SYS 1/CHAN A/115VAC | 49HH | X22 |
| 122VU | AIR COND/TEMP CTL SYS 1/CHAN A/28VDC | 51HH | X21 |
| 122VU | AIR COND/TEMP CTL SYS 2/CHAN B/28VDC | 56HH | Y21 |
| 122VU | AIR COND/TEMP CTL SYS 2/CHAN B/115VAC | 54HH | Y20 |
| 122VU | AIR COND/TEMP CTL SYS 1/CHAN B/115VAC | 50HH | Y18 |
C. Aircraft Maintenance Configuration
(a) the PACK FLOW selector is in the NORM position and,
(b) the PACK 1 and the PACK 2 pushbutton switches are in the on position (the OFF legend is off).
(3) Do the EIS start procedure (upper ECAM DU and lower ECAM DU only)
(Ref. AMM TASK 31-60-00-860-001).
Subtask 21-63-00-860-054-B ** ON A/C NOT FOR ALL WARNING:
MAKE SURE THAT THE FWD AVIONICS ACCESS DOOR 811 IS OPEN WITH A WARNING PLACARD ATTACHED TO IT.
THE WARNING NOTICE MUST TELL PERSONS NOT TO CLOSE THE DOOR. THIS PREVENTS ACCIDENTAL PRESSURIZATION OF THE AIRCRAFT.
(1) Pre-condition the Aircraft - do the pre-conditioning with the APU (Ref. AMM TASK 12-33-21-618-001) or through the HP ground connector (Ref. AMM TASK 12-33-21-618-001) .
(a) the PACK FLOW selector is in the NORM position and,
(b) the PACK 1 and the PACK 2 pushbutton switches are in the on position (the OFF legend is off).
(3) Do the EIS start procedure (upper ECAM DU and lower ECAM DU only)
(Ref. AMM TASK 31-60-00-860-001).
C. Aircraft Maintenance Configuration
(a) the ECON FLOW pushbutton switch is in the off position (the ON legend is off) and,
(b) the PACK 1 and the PACK 2 pushbutton switches are in the on position (the OFF legends are off).
(3) Do the EIS start procedure (upper ECAM DU and lower ECAM DU only)
(Ref. AMM TASK 31-60-00-860-001).
4. ProcedureWARNING:
MAKE SURE THAT THE FWD AVIONICS ACCESS DOOR 811 IS OPEN WITH A WARNING PLACARD ATTACHED TO IT.
THE WARNING NOTICE MUST TELL PERSONS NOT TO CLOSE THE DOOR. THIS PREVENTS ACCIDENTAL PRESSURIZATION OF THE AIRCRAFT.
(1) Pre-condition the Aircraft - do the pre-conditioning with the APU (Ref. AMM TASK 12-33-21-618-001) or through the HP ground connector (Ref. AMM TASK 12-33-21-618-001) .
(a) the ECON FLOW pushbutton switch is in the off position (the ON legend is off) and,
(b) the PACK 1 and the PACK 2 pushbutton switches are in the on position (the OFF legends are off).
(3) Do the EIS start procedure (upper ECAM DU and lower ECAM DU only)
(Ref. AMM TASK 31-60-00-860-001).
Subtask 21-63-00-720-050-B
WARNING:
MAKE SURE THAT THERE ARE NO PERSONS OR EQUIPMENT NEAR THE RAM AIR OUTLETS.
HOT EXHAUST GASES CAN CAUSE INJURY TO PERSONS AND/OR DAMAGE TO EQUIPMENT.
A. Functional Test of the Temperature Control System NOTE: Make sure that the cabin doors and the cockpit windows are closed when you do the test.
NOTE: Due to low pressure in the trim system, with fully closed trim air valves the trim-air pressure regulating-valve symbol (6) can be indicated as closed and show amber.
You must ignore this indication for the purposes of this test.
You must ignore this indication for the purposes of this test.
| ACTION | RESULT |
|---|---|
1.On the ECAM control panel:
| On the System Display (SD):
|
2.On the AIR COND panel 30VU:
| |
3.On the ECAM control panel:
| On the SD:
|
| 4.Wait until the CKPT, the FWD and the AFT zone temperatures (5) have stabilized at 24 deg.C (75.20 deg.F). | On the SD (COND page):
|
5.On the AIR COND panel 30VU:
| On the SD (COND page):
|
6.On the ECAM control panel:
| On the SD:
|
7.On the AIR COND panel 30VU:
| On the SD (BLEED page):
|
8.On the ECAM control panel:
| On the SD:
|
Subtask 21-63-00-860-055-A
A. Aircraft Maintenance Configuration
(1) On the AIR COND panel 30VU put the cockpit and the cabin TEMP selectors to the 12 o'clock position.
(2) Push the PACK 1 and the PACK 2 pushbutton switches to the off position (the OFF legends are on).
(3) Do the EIS stop procedure
(Ref. AMM TASK 31-60-00-860-002).
(4) Stop the pre-conditioning with the APU (Ref. AMM TASK 12-33-21-618-001) or through the HP ground connector (Ref. AMM TASK 12-33-21-618-001) .
Subtask 21-63-00-862-061-A (1) On the AIR COND panel 30VU put the cockpit and the cabin TEMP selectors to the 12 o'clock position.
(2) Push the PACK 1 and the PACK 2 pushbutton switches to the off position (the OFF legends are on).
(3) Do the EIS stop procedure
(Ref. AMM TASK 31-60-00-860-002).
(4) Stop the pre-conditioning with the APU (Ref. AMM TASK 12-33-21-618-001) or through the HP ground connector (Ref. AMM TASK 12-33-21-618-001) .
System Display Pages - Component Location