Cleaning of the Avionics-Compartment Smoke-Detector Piccolo-Tubes
TASK 26-15-00-100-001-A
Cleaning of the Avionics-Compartment Smoke-Detector Piccolo-Tubes
Refer to the MPD TASK: 261500-03
CLEAN AVIONICS SMOKE DETECTION PICCOLO TUBES
2. Job Set-up Information
A. Fixtures, Tools, Test and Support Equipment
B. Work Zones and Access Panels
C. Referenced Information
3. Job Set-up
Subtask 26-15-00-861-052-A Subtask 26-15-00-010-051-A
Subtask 26-15-00-100-050-A
Subtask 26-15-00-420-050-A
[Rev.10 from 2021]
2026.03.31 23:43:45 UTC
Cleaning of the Avionics-Compartment Smoke-Detector Piccolo-Tubes
ZONE: 128
1. Reason for the JobRefer to the MPD TASK: 261500-03
CLEAN AVIONICS SMOKE DETECTION PICCOLO TUBES
2. Job Set-up Information
A. Fixtures, Tools, Test and Support Equipment
| REFERENCE | QTY | DESIGNATION |
|---|---|---|
| No specific | 1 | ACCESS PLATFORM 2M (6 FT) - ADJUSTABLE |
| No specific | 1 | AIR SOURCE 0.3 TO 0.7 BAR (5 TO 10 PSI)- FILTERED, DRY |
| ZONE/ACCESS | ZONE DESCRIPTION |
|---|---|
| 128 | REAR AVIONIC COMPARTMENT |
| 824 |
| REFERENCE | DESIGNATION |
|---|---|
| TASK 21-26-41-000-002-A | Removal of the Air Extraction Duct |
| TASK 21-26-41-400-002-A | Installation of the Air Extraction Duct |
| TASK 24-42-00-861-001-A | Energize the Ground Service Network from the External Power |
| TASK 24-42-00-862-001-A | De-energize the Ground Service Network Supplied from the External Power |
| TASK 26-15-00-710-001-A | Operational Test of the Avionics Smoke Detection |
| TASK 26-15-15-000-001-A | Removal of the Smoke Detector - Avionics Compartment |
| TASK 26-15-15-400-001-A | Installation of the Smoke Detector - Avionics Compartment |
| TASK 52-41-00-410-002-A | Close the Avionics Compartment Doors after Access |
Subtask 26-15-00-861-052-A Subtask 26-15-00-010-051-A
B. Get Access
(1) Put the ACCESS PLATFORM 2M (6 FT) - ADJUSTABLE in position at the access door 824.
(2) Open the access door 824.
Subtask 26-15-00-020-050-A (1) Put the ACCESS PLATFORM 2M (6 FT) - ADJUSTABLE in position at the access door 824.
(2) Open the access door 824.
C. Removal of the Duct
(1) Remove the avionics compartment smoke detector (Ref. AMM TASK 26-15-15-000-001).
(2) Remove the duct (Ref. AMM TASK 21-26-41-000-002).
4. Procedure(1) Remove the avionics compartment smoke detector (Ref. AMM TASK 26-15-15-000-001).
(2) Remove the duct (Ref. AMM TASK 21-26-41-000-002).
Subtask 26-15-00-100-050-A
A. Cleaning of the Piccolo Tubes
(2) Use an AIR SOURCE 0.3 TO 0.7 BAR (5 TO 10 PSI)- FILTERED, DRY to clean the piccolo tubes.
(3) Make sure that the piccolo tubes are in the correct condition and that there is no unwanted material in the duct.
5. Close-upWARNING:
WHEN YOU USE COMPRESSED AIR:
(1) Make sure that the output tubes have no blockage. If necessary clean the output tubes with compressed air. - USE THE CORRECT PROTECTION (FACE SHIELD OR GOGGLES)
- DO NOT POINT THE AIRFLOW AT YOURSELF OR OTHER PERSONS.
(2) Use an AIR SOURCE 0.3 TO 0.7 BAR (5 TO 10 PSI)- FILTERED, DRY to clean the piccolo tubes.
(3) Make sure that the piccolo tubes are in the correct condition and that there is no unwanted material in the duct.
Subtask 26-15-00-420-050-A
A. Installation of the Duct
(1) Install the duct (Ref. AMM TASK 21-26-41-400-002).
(2) Install the avionics compartment smoke detector (Ref. AMM TASK 26-15-15-400-001).
Subtask 26-15-00-710-052-A (1) Install the duct (Ref. AMM TASK 21-26-41-400-002).
(2) Install the avionics compartment smoke detector (Ref. AMM TASK 26-15-15-400-001).
B. Operational Test
(1) Do the operational test of the avionics smoke detection system from the Multipurpose Control and Display Unit (MCDU) (Ref. AMM TASK 26-15-00-710-001).
Subtask 26-15-00-410-051-A (1) Do the operational test of the avionics smoke detection system from the Multipurpose Control and Display Unit (MCDU) (Ref. AMM TASK 26-15-00-710-001).
C. Close Access
(1) Make sure that the work area is clean and clear of tools and other items.
(2) Close the access door 824 (Ref. AMM TASK 52-41-00-410-002).
(3) Remove the access platform(s).
Subtask 26-15-00-862-052-A (1) Make sure that the work area is clean and clear of tools and other items.
(2) Close the access door 824 (Ref. AMM TASK 52-41-00-410-002).
(3) Remove the access platform(s).
Avionics-Compartment Smoke-Detector Piccolo-Tubes