Functional Test of Ionic Smoke Detector Sensitivity
TASK 26-15-00-720-001-A
Functional Test of Ionic Smoke Detector Sensitivity
1. Reason for the Job
A. Fixtures, Tools, Test and Support Equipment
B. Work Zones and Access Panels
C. Referenced Information
3. Job Set-up
Subtask 26-15-00-861-050-A
Subtask 26-15-00-720-050-A
Subtask 26-15-00-080-050-A
[Rev.10 from 2021]
2026.03.31 23:43:44 UTC
Functional Test of Ionic Smoke Detector Sensitivity
1. Reason for the Job
NOTE: Make sure that the detector is not dirty.
NOTE: This task is applicable only on aircraft with ionic smoke detector installed.
2. Job Set-up InformationA. Fixtures, Tools, Test and Support Equipment
| REFERENCE | QTY | DESIGNATION |
|---|---|---|
| No specific | 1 | ACCESS PLATFORM 2M (6 FT) - ADJUSTABLE |
| No specific | AR | SAFETY CLIP - CIRCUIT BREAKER |
| 35M5M01130000 | 1 | TEST SET-SMOKE DETECTOR |
| ZONE/ACCESS | ZONE DESCRIPTION |
|---|---|
| 824 |
| REFERENCE | DESIGNATION |
|---|---|
| TASK 24-42-00-861-001-A | Energize the Ground Service Network from the External Power |
| TASK 24-42-00-862-001-A | De-energize the Ground Service Network Supplied from the External Power |
| TASK 26-15-00-710-001-A | Operational Test of the Avionics Smoke Detection |
| TASK 26-15-15-000-001-A | Removal of the Smoke Detector - Avionics Compartment |
| TASK 26-15-15-400-001-A | Installation of the Smoke Detector - Avionics Compartment |
| TASK 52-41-00-410-002-A | Close the Avionics Compartment Doors after Access |
Subtask 26-15-00-861-050-A
A. Energization
Subtask 26-15-00-865-058-A CAUTION:
USE ONLY THE GROUND SERVICE NETWORK TO SUPPLY ELECTRICITY BECAUSE THE AVIONICS VENTILATION SYSTEM IS NOT SERVICEABLE. IF YOU ENERGIZE THE AIRCRAFT ELECTRICAL CIRCUITS WITHOUT THE VENTILATION SYSTEM YOU WILL CAUSE DAMAGE TO ELECTRICAL EQUIPMENT.
(1) Energize the ground service network (Ref. AMM TASK 24-42-00-861-001). B. Open, safety and tag this(these) circuit breaker(s):
Subtask 26-15-00-010-050-A | PANEL | DESIGNATION | FIN | LOCATION |
|---|---|---|---|
| ** ON A/C ALL | |||
| 49VU | AIR COND/AVNCS VENT/CTL | 6HQ | D06 |
| 49VU | AIR COND/AVNCS VENT/CTL | 5HQ | D05 |
C. Get Access
(1) Put the ACCESS PLATFORM 2M (6 FT) - ADJUSTABLE in position at the access door 824.
(2) Open the access door 824.
Subtask 26-15-00-480-050-A (1) Put the ACCESS PLATFORM 2M (6 FT) - ADJUSTABLE in position at the access door 824.
(2) Open the access door 824.
D. Connection of the Tooling
(1) Disconnect the electrical connector 1WA-A from the smoke detector 1WA.
(2) Connect the electrical connector of the 35M5M01130000 TEST SET-SMOKE DETECTOR to the connector of the smoke detector 1WA ; the voltage of the electrical power supply is 28V, supplied by the test set.
4. Procedure(1) Disconnect the electrical connector 1WA-A from the smoke detector 1WA.
(2) Connect the electrical connector of the 35M5M01130000 TEST SET-SMOKE DETECTOR to the connector of the smoke detector 1WA ; the voltage of the electrical power supply is 28V, supplied by the test set.
Subtask 26-15-00-720-050-A
A. Functional Test of Smoke Detector Sensitivity
5. Close-up| ACTION | RESULT |
|---|---|
| 1.On the test set : | On the test set : |
| |
| |
| |
|
|
| |
|
|
| | The detector sensitivity is :
|
Subtask 26-15-00-080-050-A
A. Disconnection of the Tooling
(1) Disconnect the electrical connector from the test set.
(2) Connect the electrical connector 1WA-A to the smoke detector 1WA.
Subtask 26-15-00-865-059-A (1) Disconnect the electrical connector from the test set.
(2) Connect the electrical connector 1WA-A to the smoke detector 1WA.
B. Remove the safety clip(s) and the tag(s) and close this(these) circuit breaker(s):
Subtask 26-15-00-710-051-A | PANEL | DESIGNATION | FIN | LOCATION |
|---|---|---|---|
| ** ON A/C ALL | |||
| 49VU | AIR COND/AVNCS VENT/CTL | 6HQ | D06 |
| 49VU | AIR COND/AVNCS VENT/CTL | 5HQ | D05 |
C. Do the operational test of the avionics smoke detection system from the Multipurpose Control and Display Unit (MCDU) (Ref. AMM TASK 26-15-00-710-001).
Subtask 26-15-00-410-050-A D. Close Access
(1) Make sure that the work area is clean and clear of tools and other items.
(2) Close the access door 824 (Ref. AMM TASK 52-41-00-410-002).
(3) Remove the access platform(s).
Subtask 26-15-00-862-050-A (1) Make sure that the work area is clean and clear of tools and other items.
(2) Close the access door 824 (Ref. AMM TASK 52-41-00-410-002).
(3) Remove the access platform(s).