Loss of the ADR1 Data Identified by the EFCS2
TASK 34-13-81-810-814-A
Loss of the ADR1 Data Identified by the EFCS2
1. Possible Causes
A. Referenced Information
3. Fault Confirmation
Subtask 34-13-81-740-076-A
Subtask 34-13-81-810-063-A ** ON A/C NOT FOR ALL
[Rev.8 from Aug 2018]
2026.04.04 04:32:34 UTC
Loss of the ADR1 Data Identified by the EFCS2
1. Possible Causes
- PROBE-PITOT, 1 [9DA1]
- PROBE-PITOT, 2 [9DA2]
- PROBE-PITOT, 3 [9DA3]
- SENSOR-ANGLE OF ATTACK, 1 [3FP1]
- SENSOR-ANGLE OF ATTACK, 2 [3FP2]
- SENSOR-ANGLE OF ATTACK, 3 [3FP3]
- ADM-L TOTAL PRESSURE [19FP1]
- ADM-R TOTAL PRESSURE [19FP2]
- ADM-STBY TOTAL PRESSURE [19FP3]
- ADM-R STATIC PRESSURE [19FP4]
- ADM-L STATIC PRESSURE [19FP5]
- ADM-R STATIC PRESSURE [19FP6]
- ADM-L STATIC PRESSURE [19FP7]
- ADM-STBY STATIC PRESSURE [19FP8]
- ADIRU-1 [1FP1]
A. Referenced Information
| REFERENCE | DESIGNATION |
|---|---|
| TSM TASK 34-11-00-810-861-A | Different Angle of Attack Value on the three ADIRUs |
| TSM TASK 34-13-81-810-823-A | Runaway or Drift of One ADR1 Parameter Identified by the ELACs and the SECs |
| AMM 30-31-00-720-001 | Functional Check of the Insulation Resistance of the Pitot Probe Heater |
| AMM 34-10-00-170-001 | Flushing of the Principal Total Pressure Lines |
| AMM 34-10-00-170-003 | Draining and Flushing of Standby Pneumatic Circuits |
| AMM 34-11-15-000-001 | Removal of the Pitot Probe |
| AMM 34-11-15-200-001 | Inspection/Check of the Pitot Probe |
| AMM 34-11-15-400-001 | Installation of the Pitot Probe |
| AMM 34-11-17-000-001 | Removal of the Air Data Module |
| AMM 34-11-17-400-001 | Installation of the Air Data Module |
| AMM 34-11-19-000-001 | Removal of the Angle of Attack Sensor |
| AMM 34-11-19-200-001 | Inspection of the Angle-Of-Attack Sensor |
| AMM 34-11-19-400-001 | Installation of the Angle of Attack Sensor |
| AMM 34-12-34-000-001 | Removal of the ADIRU |
| AMM 34-12-34-400-001 | Installation of the ADIRU |
| AMM 34-13-00-720-010 | Functional Test of the ADM Accuracy |
Subtask 34-13-81-740-076-A
A. Not applicable, you cannot confirm this fault on the ground.
4. Fault IsolationSubtask 34-13-81-810-063-A ** ON A/C NOT FOR ALL
A. Read the Post Flight Report (PFR) for the maintenance messages related to the link between SEC and ADR.
(1) If the PFR gives the maintenance message(s) SEC1 OR BUS3 FROM ADR3 and/or SEC2 OR BUS 2 FROM ADR2:
(a) Do this trouble shooting procedure: (Ref. TSM TASK 34-13-81-810-823).
(2) If the PFR does not give the above maintenance message(s):
(a) Do the inspection/check of the pitot probes (9DA1, 9DA2 and 9DA3) AMM 34-11-15-200-001.
1 If one pitot probe is damaged:
1 If one angle-of-attack sensor is damaged:
(d) Do the functional test of the insulation resistance of the pitot probe heaters (9DA1, 9DA2 and 9DA3) AMM 30-31-00-720-001.
1 If the test is not OK:
(f) Do the draining and flushing of the standby pneumatic circuits AMM 34-10-00-170-003.
1 If the fault continues after the subsequent flight:
Subtask 34-13-81-810-063-B ** ON A/C NOT FOR ALL (1) If the PFR gives the maintenance message(s) SEC1 OR BUS3 FROM ADR3 and/or SEC2 OR BUS 2 FROM ADR2:
(a) Do this trouble shooting procedure: (Ref. TSM TASK 34-13-81-810-823).
(2) If the PFR does not give the above maintenance message(s):
(a) Do the inspection/check of the pitot probes (9DA1, 9DA2 and 9DA3) AMM 34-11-15-200-001.
1 If one pitot probe is damaged:
- replace the defective pitot probe PROBE-PITOT, 1 [9DA1] , PROBE-PITOT, 2 [9DA2] or PROBE-PITOT, 3 [9DA3] AMM 34-11-15-000-001 and AMM 34-11-15-400-001.
1 If one angle-of-attack sensor is damaged:
- replace the defective angle-of-attack sensor: SENSOR-ANGLE OF ATTACK, 1 [3FP1] , SENSOR-ANGLE OF ATTACK, 2 [3FP2] or SENSOR-ANGLE OF ATTACK, 3 [3FP3] AMM 34-11-19-000-001 and AMM 34-11-19-400-001.
(d) Do the functional test of the insulation resistance of the pitot probe heaters (9DA1, 9DA2 and 9DA3) AMM 30-31-00-720-001.
1 If the test is not OK:
- replace the defective pitot probe: PROBE-PITOT, 1 [9DA1] , PROBE-PITOT, 2 [9DA2] or PROBE-PITOT, 3 [9DA3] AMM 34-11-15-000-001 and AMM 34-11-15-400-001.
(f) Do the draining and flushing of the standby pneumatic circuits AMM 34-10-00-170-003.
1 If the fault continues after the subsequent flight:
- do the functional test of the ADM accuracy (19FP1 to 19FP8) AMM 34-13-00-720-010.
- replace the defective air data module: ADM-L TOTAL PRESSURE [19FP1] , ADM-R TOTAL PRESSURE [19FP2] , ADM-STBY TOTAL PRESSURE [19FP3] , ADM-R STATIC PRESSURE [19FP4] , ADM-L STATIC PRESSURE [19FP5] , ADM-R STATIC PRESSURE [19FP6] , ADM-L STATIC PRESSURE [19FP7] or ADM-STBY STATIC PRESSURE [19FP8] AMM 34-11-17-000-001 and AMM 34-11-17-400-001.
- replace the SENSOR-ANGLE OF ATTACK, 1 [3FP1] AMM 34-11-19-000-001 and AMM 34-11-19-400-001.
- replace the ADIRU-1 [1FP1] AMM 34-12-34-000-001 and AMM 34-12-34-400-001.
A. Read the Post Flight Report (PFR) for the maintenance messages related to the link between SEC and ADR.
(1) If the PFR gives the maintenance message(s) SEC1 OR BUS3 FROM ADR3 and/or SEC2 OR BUS 2 FROM ADR2:
(a) Do the inspection/check of the pitot probes (9DA1, 9DA2 and 9DA3) AMM 34-11-15-200-001.
1 If one pitot probe is damaged:
1 If the test is not OK:
(1) If the PFR gives the maintenance message(s) SEC1 OR BUS3 FROM ADR3 and/or SEC2 OR BUS 2 FROM ADR2:
- do this trouble shooting procedure: (Ref. TSM TASK 34-13-81-810-823).
(a) Do the inspection/check of the pitot probes (9DA1, 9DA2 and 9DA3) AMM 34-11-15-200-001.
1 If one pitot probe is damaged:
- replace the defective pitot probe: PROBE-PITOT, 1 [9DA1] , PROBE-PITOT, 2 [9DA2] or PROBE-PITOT, 3 [9DA3] AMM 34-11-15-000-001 and AMM 34-11-15-400-001.
1 If the test is not OK:
- replace the defective pitot probe: PROBE-PITOT, 1 [9DA1] , PROBE-PITOT, 2 [9DA2] or PROBE-PITOT, 3 [9DA3] AMM 34-11-15-000-001 and AMM 34-11-15-400-001.
- do the draining and flushing of standby pneumatic circuits AMM 34-10-00-170-003.
- do the functional test of the ADM accuracy (19FP1 to 19FP8) AMM 34-13-00-720-010.
- replace the defective air data module: ADM-L TOTAL PRESSURE [19FP1] , ADM-R TOTAL PRESSURE [19FP2] , ADM-STBY TOTAL PRESSURE [19FP3] , ADM-R STATIC PRESSURE [19FP4] , ADM-L STATIC PRESSURE [19FP5] , ADM-R STATIC PRESSURE [19FP6] , ADM-L STATIC PRESSURE [19FP7] or ADM-STBY STATIC PRESSURE [19FP8] AMM 34-11-17-000-001 and AMM 34-11-17-400-001.
- replace the ADIRU-1 [1FP1] AMM 34-12-34-000-001 and AMM 34-12-34-400-001.