W DOC AIRBUS | TSM A320F

Loss of the THS Command Transducer Signal for the SEC 2


TASK 27-94-00-810-839-A
Loss of the THS Command Transducer Signal for the SEC 2


1. Possible Causes
  • SEC-2 [1CE2]
  • Command Position Transducer
  • wiring of the XDCR COM SPLY signal from the THS actuator (9CE) to the first terminal block
  • wiring of the XDCR COM V1, V2 signals from the THS actuator (9CE) to the SEC 2 (1CE2)
2. Job Set-up Information
 A. Referenced Information
REFERENCE
DESIGNATION
TSM TASK 27-90-00-810-821-A
Loss of the ACS1 Signal of the SEC2 COM Side
TSM TASK 27-90-00-810-823-A
Loss of the ACS1 Signal of the ELAC2 COM Side and SEC2 COM Side
AMM 27-44-56-000-001
Removal of the Position Transducer from the THS Actuator
AMM 27-44-56-400-001
Installation of the Position Transducer to the THS Actuator
ASM 279413
AMM 27-94-34-000-001
Removal of the SEC
AMM 27-94-34-400-001
Installation of the SEC
AMM 27-96-00-710-022
Operational Test of the THS Actuator Electrical Control (Activation for BITE Test)
AMM 27-96-00-740-001
BITE Test of the EFCS (Ground Scanning)
3. Fault Confirmation
Subtask 27-94-00-700-094-A
A. Test
   (1) Do the operational test of the THS actuator electrical control AMM 27-96-00-710-022.
NOTE: Do the ground setting only with the SEC 2.
   (2) Do the BITE test of the EFCS (Ground Scanning) AMM 27-96-00-740-001.
     (a) If the ground scanning gives the maintenance message:
SEC2 COM OR INPUT OF THS ACTR XDCR3 9CE
  • refer to Para. Fault Isolation.
     (b) If the ground scanning gives at least two maintenance messages of the list below:
SEC2 OR WIRING FROM L G ELEV POS XDCR 34CE1
SEC2 OR WIRING FROM R Y ELEV POS XDCR 34CE2
SEC2 COM OR INPUT OF THS ACTR XDCR3 9CE
     (c) If the ground scanning gives at least two maintenance messages of the list below:
L G ELEV POS XDCR 34CE1 COM E2/S2:USE STBY XDCR
R Y ELEV POS XDCR 34CE2 COM E2/S2:USE STBY XDCR
ELAC2 COM OR INPUT OF THS ACTR XDCR1 9CE
SEC2 COM OR INPUT OF THS ACTR XDCR3 9CE
4. Fault Isolation
Subtask 27-94-00-810-088-A
A. If the BITE test gives the maintenance message:
SEC2 COM OR INPUT OF THS ACTR XDCR3 9CE
   (1) If the fault continues:
   (2) If the fault continues:
  • do a check of the wiring of the XDCR COM SPLY signal from the THS actuator (9CE) to the first terminal block, ASM 279413.
     (a) If there is no continuity, repair the wiring.
     (b) If there is continuity:
  • do a check and repair the wiring of the XDCR COM V1, V2 signals from the THS actuator (9CE) to the SEC 2 (1CE2), ASM 279413.
Subtask 27-94-00-700-095-A
B. Do the tests given in Para. 3.