Loss of the THS Command Transducer Signal for the SEC 2
TASK 27-94-00-810-839-A
Loss of the THS Command Transducer Signal for the SEC 2
1. Possible Causes
A. Referenced Information
3. Fault Confirmation
Subtask 27-94-00-700-094-A
Subtask 27-94-00-810-088-A
[Rev.8 from Aug 2018]
2026.04.04 04:28:14 UTC
Loss of the THS Command Transducer Signal for the SEC 2
1. Possible Causes
- SEC-2 [1CE2]
- Command Position Transducer
wiring of the XDCR COM SPLY signal from the THS actuator (9CE) to the first terminal block wiring of the XDCR COM V1, V2 signals from the THS actuator (9CE) to the SEC 2 (1CE2)
A. Referenced Information
| REFERENCE | DESIGNATION |
|---|---|
| TSM TASK 27-90-00-810-821-A | Loss of the ACS1 Signal of the SEC2 COM Side |
| TSM TASK 27-90-00-810-823-A | Loss of the ACS1 Signal of the ELAC2 COM Side and SEC2 COM Side |
| AMM 27-44-56-000-001 | Removal of the Position Transducer from the THS Actuator |
| AMM 27-44-56-400-001 | Installation of the Position Transducer to the THS Actuator |
| ASM 279413 | |
| AMM 27-94-34-000-001 | Removal of the SEC |
| AMM 27-94-34-400-001 | Installation of the SEC |
| AMM 27-96-00-710-022 | Operational Test of the THS Actuator Electrical Control (Activation for BITE Test) |
| AMM 27-96-00-740-001 | BITE Test of the EFCS (Ground Scanning) |
Subtask 27-94-00-700-094-A
A. Test
(1) Do the operational test of the THS actuator electrical control AMM 27-96-00-710-022.
(a) If the ground scanning gives the maintenance message:
SEC2 COM OR INPUT OF THS ACTR XDCR3 9CE
SEC2 OR WIRING FROM L G ELEV POS XDCR 34CE1
SEC2 OR WIRING FROM R Y ELEV POS XDCR 34CE2
SEC2 COM OR INPUT OF THS ACTR XDCR3 9CE
L G ELEV POS XDCR 34CE1 COM E2/S2:USE STBY XDCR
R Y ELEV POS XDCR 34CE2 COM E2/S2:USE STBY XDCR
ELAC2 COM OR INPUT OF THS ACTR XDCR1 9CE
SEC2 COM OR INPUT OF THS ACTR XDCR3 9CE
4. Fault Isolation(1) Do the operational test of the THS actuator electrical control AMM 27-96-00-710-022.
NOTE: Do the ground setting only with the SEC 2.
(2) Do the BITE test of the EFCS (Ground Scanning) AMM 27-96-00-740-001. (a) If the ground scanning gives the maintenance message:
SEC2 COM OR INPUT OF THS ACTR XDCR3 9CE
- refer to Para. Fault Isolation.
SEC2 OR WIRING FROM L G ELEV POS XDCR 34CE1
SEC2 OR WIRING FROM R Y ELEV POS XDCR 34CE2
SEC2 COM OR INPUT OF THS ACTR XDCR3 9CE
- do this trouble shooting procedure (Ref. TSM TASK 27-90-00-810-821).
L G ELEV POS XDCR 34CE1 COM E2/S2:USE STBY XDCR
R Y ELEV POS XDCR 34CE2 COM E2/S2:USE STBY XDCR
ELAC2 COM OR INPUT OF THS ACTR XDCR1 9CE
SEC2 COM OR INPUT OF THS ACTR XDCR3 9CE
- do this trouble shooting procedure (Ref. TSM TASK 27-90-00-810-823).
Subtask 27-94-00-810-088-A
A. If the BITE test gives the maintenance message:
SEC2 COM OR INPUT OF THS ACTR XDCR3 9CE
(b) If there is continuity:
Subtask 27-94-00-700-095-A SEC2 COM OR INPUT OF THS ACTR XDCR3 9CE
- replace the SEC-2 [1CE2] , AMM 27-94-34-000-001 and AMM 27-94-34-400-001.
- replace the Command Position Transducer , AMM 27-44-56-000-001 and AMM 27-44-56-400-001.
- do a check of the
wiring of the XDCR COM SPLY signal from the THS actuator (9CE) to the first terminal block , ASM 279413.
(b) If there is continuity:
- do a check and repair the
wiring of the XDCR COM V1, V2 signals from the THS actuator (9CE) to the SEC 2 (1CE2) , ASM 279413.
B. Do the tests given in Para. 3.