Failure of the THS Monitor Transducer 2
TASK 27-93-00-810-840-A
Failure of the THS Monitor Transducer 2
1. Possible Causes
A. Referenced Information
3. Fault Confirmation
Subtask 27-93-00-700-092-A
Subtask 27-93-00-810-089-A
[Rev.8 from Aug 2018]
2026.04.04 04:27:57 UTC
Failure of the THS Monitor Transducer 2
1. Possible Causes
- monitor position transducer
- command position transducer
wiring of the XDCR MON SPLY signal from the THS actuator (9CE) to the first terminal block wiring of the XDCR MON V1, V2 signals from the THS actuator (9CE) to the first terminal block wiring of the XDCR COM SPLY signal from the THS actuator (9CE) to the first terminal block wiring of the XDCR COM V1, V2 signals from the THS actuator (9CE) to the first terminal block
A. Referenced Information
| REFERENCE | DESIGNATION |
|---|---|
| TSM TASK 27-90-00-810-820-A | Loss of the ACS1 Signal of the ELAC1 MON Side and SEC1 MON Side |
| TSM TASK 31-32-00-810-933-A | Failure of the Analog Links |
| AMM 27-44-56-000-001 | Removal of the Position Transducer from the THS Actuator |
| AMM 27-44-56-400-001 | Installation of the Position Transducer to the THS Actuator |
| ASM 279312 | |
| ASM 279412 | |
| AMM 27-96-00-710-022 | Operational Test of the THS Actuator Electrical Control (Activation for BITE Test) |
| AMM 27-96-00-740-001 | BITE Test of the EFCS (Ground Scanning) |
Subtask 27-93-00-700-092-A
A. Test
(1) Do the operational test of the THS actuator electrical control AMM 27-96-00-710-022.
(a) If the ground scanning gives the maintenance message:
THS ACTR XDCR2 MON 9CE
L ELEV POS MON XDCR OF ELAC1/SEC1
L G ELEV MODE XDCR 34CE1
R B ELEV POS MON XDCR OF ELAC1/SEC1
R Y ELEV MODE XDCR 34CE2
THS ACTR XDCR2 MON 9CE
4. Fault Isolation(1) Do the operational test of the THS actuator electrical control AMM 27-96-00-710-022.
NOTE: Do the ground setting only with the ELAC 1.
(2) Do the BITE test of the EFCS (ground scanning) AMM 27-96-00-740-001. (a) If the ground scanning gives the maintenance message:
THS ACTR XDCR2 MON 9CE
- refer to Para. Fault Isolation.
L ELEV POS MON XDCR OF ELAC1/SEC1
L G ELEV MODE XDCR 34CE1
R B ELEV POS MON XDCR OF ELAC1/SEC1
R Y ELEV MODE XDCR 34CE2
THS ACTR XDCR2 MON 9CE
- do this trouble shooting procedure (Ref. TSM TASK 27-90-00-810-820).
Subtask 27-93-00-810-089-A
A. If the BITE test gives the maintenance message:
THS ACTR XDCR2 MON 9CE
(b) If there is continuity:
(b) If there is continuity:
Subtask 27-93-00-700-093-A THS ACTR XDCR2 MON 9CE
- Do the trouble shooting procedure (Ref. TSM TASK 31-32-00-810-933) related to the ANI 2-3 analog input signal of the ELAC 1 and SEC 1 ASM 279312 and ASM 279412.
- Replace the monitor position transducer , AMM 27-44-56-000-001 and AMM 27-44-56-400-001.
- Replace the command position transducer , AMM 27-44-56-000-001 and AMM 27-44-56-400-001.
- Do a check of the
wiring of the XDCR MON SPLY signal from the THS actuator (9CE) to the first terminal block , ASM 279312.
(b) If there is continuity:
- Do a check and repair the
wiring of the XDCR MON V1, V2 signals from the THS actuator (9CE) to the first terminal block , ASM 279312.
- Do a check of the
wiring of the XDCR COM SPLY signal from the THS actuator (9CE) to the first terminal block , ASM 279312.
(b) If there is continuity:
- Do a check and repair the
wiring of the XDCR COM V1, V2 signals from the THS actuator (9CE) to the first terminal block , ASM 279312.
B. Do the tests given in Para. 3.