Loss of the THS Command Transducer Signal for the ELAC 2
TASK 27-93-00-810-833-A
Loss of the THS Command Transducer Signal for the ELAC 2
1. Possible Causes
A. Referenced Information
3. Fault Confirmation
Subtask 27-93-00-700-078-A
Subtask 27-93-00-810-082-A
[Rev.8 from Aug 2018]
2026.04.04 04:27:57 UTC
Loss of the THS Command Transducer Signal for the ELAC 2
1. Possible Causes
- ELAC-2 [2CE2]
- command position transducer
wiring of the XDCR COM SPLY signal from the THS actuator (9CE) to the first terminal block wiring of the XDCR COM V1, V2 signals from the THS actuator (9CE) to the ELAC 2 (2CE2)
A. Referenced Information
| REFERENCE | DESIGNATION |
|---|---|
| TSM TASK 27-90-00-810-814-A | Loss of the ACS1 Signal of the ELAC2 COM Side |
| TSM TASK 27-90-00-810-815-A | Loss of the ACS1 Signal of the ELAC2 MON Side |
| TSM TASK 27-90-00-810-816-A | Loss of the ACS1 of the ELAC2 COM and MON Sides |
| TSM TASK 27-90-00-810-823-A | Loss of the ACS1 Signal of the ELAC2 COM Side and SEC2 COM Side |
| AMM 27-44-56-000-001 | Removal of the Position Transducer from the THS Actuator |
| AMM 27-44-56-400-001 | Installation of the Position Transducer to the THS Actuator |
| ASM 279313 | |
| AMM 27-93-34-000-001 | Removal of the ELAC |
| AMM 27-93-34-400-001 | Installation of the ELAC |
| AMM 27-96-00-710-022 | Operational Test of the THS Actuator Electrical Control (Activation for BITE Test) |
| AMM 27-96-00-740-001 | BITE Test of the EFCS (Ground Scanning) |
Subtask 27-93-00-700-078-A
A. Test
(1) Do the operational test of the THS actuator electrical control AMM 27-96-00-710-022.
(a) If the ground scanning gives the maintenance message:
ELAC2 COM OR INPUT OF THS ACTR XDCR1 9CE
First list:
Combination of maintenance messages of the first list, do this trouble shooting procedure (Ref. TSM TASK 27-90-00-810-814).
2 Second case:
Combination of maintenance messages of the second list, do this trouble shooting procedure (Ref. TSM TASK 27-90-00-810-815).
3 Third case:
Combination of maintenance messages of the first and second lists, do this trouble shooting procedure (Ref. TSM TASK 27-90-00-810-816).
(c) If the ground scanning gives at least two maintenance messages of the list below:
ELAC2 COM OR INPUT OF THS ACTR XDCR1 9CE
SEC2 COM OR INPUT OF THS ACTR XDCR3 9CE
L G ELEV MODE XDCR 34CE1 COM E2/S2:USE STBY XDCR
R Y ELEV MODE XDCR 34CE2 COM E2/S2:USE STBY XDCR
4. Fault Isolation(1) Do the operational test of the THS actuator electrical control AMM 27-96-00-710-022.
NOTE: Do the ground setting only with the ELAC 2.
(2) Do the BITE test of the EFCS (ground scanning) AMM 27-96-00-740-001. (a) If the ground scanning gives the maintenance message:
ELAC2 COM OR INPUT OF THS ACTR XDCR1 9CE
- refer to Para. Fault Isolation.
First list:
- ELAC2 COM OR INPUT OF THS ACTR XDCR1 9CE
- ELAC2 OR WIRING FROM L G ELEV POS XDCR 34CE1
- ELAC2 OR WIRING FROM R Y ELEV POS XDCR 34CE2
Second list: - ELAC2 MON OR INPUT OF THS ACTR XDCR1 9CE
- ELAC2 OR WIRING FROM L ELEV POS MON XDCR
- ELAC2 OR WIRING FROM R ELEV POS MON XDCR
- ELAC2 OR WIRING FROM L B ELEV MODE XDCR 34CE3
- ELAC2 OR WIRING FROM R Y ELEV MODE XDCR 34CE4
Combination of maintenance messages of the first list, do this trouble shooting procedure (Ref. TSM TASK 27-90-00-810-814).
2 Second case:
Combination of maintenance messages of the second list, do this trouble shooting procedure (Ref. TSM TASK 27-90-00-810-815).
3 Third case:
Combination of maintenance messages of the first and second lists, do this trouble shooting procedure (Ref. TSM TASK 27-90-00-810-816).
(c) If the ground scanning gives at least two maintenance messages of the list below:
ELAC2 COM OR INPUT OF THS ACTR XDCR1 9CE
SEC2 COM OR INPUT OF THS ACTR XDCR3 9CE
L G ELEV MODE XDCR 34CE1 COM E2/S2:USE STBY XDCR
R Y ELEV MODE XDCR 34CE2 COM E2/S2:USE STBY XDCR
- do this trouble shooting procedure (Ref. TSM TASK 27-90-00-810-823).
Subtask 27-93-00-810-082-A
A. If the BITE test gives the maintenance message:
ELAC2 COM OR INPUT OF THS ACTR XDCR1 9CE
(b) If there is continuity:
Subtask 27-93-00-700-079-A ELAC2 COM OR INPUT OF THS ACTR XDCR1 9CE
- replace the ELAC-2 [2CE2] , AMM 27-93-34-000-001 and AMM 27-93-34-400-001.
- replace the command position transducer , AMM 27-44-56-000-001 and AMM 27-44-56-400-001.
- do a check of the
wiring of the XDCR COM SPLY signal from the THS actuator (9CE) to the first terminal block , ASM 279313.
(b) If there is continuity:
- do a check and repair the
wiring of the XDCR COM V1, V2 signals from the THS actuator (9CE) to the ELAC 2 (2CE2) , ASM 279313.
B. Do the tests given in Para. 3.