Failure of the Right Elevator Position MON Transducer
TASK 27-30-00-810-825-A
Failure of the Right Elevator Position MON Transducer
1. Possible Causes
A. Referenced Information
3. Fault Confirmation
Subtask 27-30-00-700-127-A
Subtask 27-30-00-810-089-C
[Rev.8 from Aug 2018]
2026.04.04 04:27:32 UTC
Failure of the Right Elevator Position MON Transducer
1. Possible Causes
- XDCR UNIT-ELEV POS, R [49CE2]
- wiring of the POS RVDT MON SPLY signal
wiring of the POS RVDT MON V1, V2 signals
A. Referenced Information
| REFERENCE | DESIGNATION |
|---|---|
| TSM TASK 27-90-00-810-820-A | Loss of the ACS1 Signal of the ELAC1 MON Side and SEC1 MON Side |
| TSM TASK 31-32-00-810-933-A | Failure of the Analog Links |
| AMM 27-92-13-000-001 | Removal of the Elevator Position Transducer-Unit |
| AMM 27-92-13-400-001 | Installation of the Elevator Position Transducer-Unit |
| ASM 279307 | |
| ASM 279407 | |
| AMM 27-96-00-710-020 | Operational Test of the Side Stick Assembly (Activation for the BITE Test) |
| AMM 27-96-00-740-001 | BITE Test of the EFCS (Ground Scanning) |
Subtask 27-30-00-700-127-A
A. Test
(1) Do the operational test of the side stick assembly (Activation for the BITE test) AMM 27-96-00-710-020.
(2) Do the BITE test of the EFCS (Ground Scanning) AMM 27-96-00-740-001.
(a) If the ground scanning gives the maintenance message:
R ELEV POS MON XDCR OF ELAC1/SEC1
L ELEV POS MON XDCR OF ELAC1/SEC1
L G ELEV MODE XDCR 34CE1
R ELEV POS MON XDCR OF ELAC1/SEC1
R Y ELEV MODE XDCR 34CE2
THS ACTR XDCR2 MON 9CE
4. Fault Isolation(1) Do the operational test of the side stick assembly (Activation for the BITE test) AMM 27-96-00-710-020.
(2) Do the BITE test of the EFCS (Ground Scanning) AMM 27-96-00-740-001.
(a) If the ground scanning gives the maintenance message:
R ELEV POS MON XDCR OF ELAC1/SEC1
- refer to Para. Fault Isolation.
L ELEV POS MON XDCR OF ELAC1/SEC1
L G ELEV MODE XDCR 34CE1
R ELEV POS MON XDCR OF ELAC1/SEC1
R Y ELEV MODE XDCR 34CE2
THS ACTR XDCR2 MON 9CE
- do this trouble shooting procedure (Ref. TSM TASK 27-90-00-810-820).
Subtask 27-30-00-810-089-C
A. If the test gives the maintenance message R ELEV POS MON XDCR OF ELAC1/SEC1:
(a) Do a check of the wiring of the POS RVDT MON SPLY signal from the transducer unit (49CE2) plug B to the first terminal block ASM 279307 .
wiring of the POS RVDT MON V1, V2 signals from the transducer unit (49CE2), plug B to the first terminal block ASM 279307.
Subtask 27-30-00-700-128-A - disconnect and cross the electrical connectors of the elevator position transducer unit (49CE2) ASM 279307 and do the test given in Para. 3.
NOTE: After the test connect the electrical connetors on their initial plugs.
(1) If the fault continues: - do the trouble shooting procedure (Ref. TSM TASK 31-32-00-810-933) related to the ANI 2-X analog input signal of the ELAC COM and SEC COM ASM 279307 and ASM 279407.
- replace the XDCR UNIT-ELEV POS, R [49CE2] AMM 27-92-13-000-001 and AMM 27-92-13-400-001.
NOTE: The resistance of primary and secondary windings must be between 30 ohms and 500 ohms.
(3) If the test gives the maintenance message R ELEV POS MON XDCR OF ELAC1/SEC1: (a) Do a check of the wiring of the POS RVDT MON SPLY signal from the transducer unit (49CE2) plug B to the first terminal block ASM 279307 .
- If there is continuity see Para. (b).
- If there is no continuity repair the above wiring.
B. Do the test given in Para. 3.