Pack 2 Controller (ACSC 2) Fault - Outlet Temperature / Compressor Outlet Temperature Indication replaced by Amber XX
TASK 21-61-00-810-854-A
Pack 2 Controller (ACSC 2) Fault - Outlet Temperature / Compressor Outlet Temperature Indication replaced by Amber XX
1. Possible Causes
2. Job Set-up Information
A. Referenced Information
3. Fault Confirmation
Subtask 21-61-00-710-142-A ** ON A/C NOT FOR ALL
Subtask 21-61-00-810-170-A ** ON A/C NOT FOR ALL
[Rev.8 from Aug 2018]
2026.04.04 04:24:55 UTC
Pack 2 Controller (ACSC 2) Fault - Outlet Temperature / Compressor Outlet Temperature Indication replaced by Amber XX
1. Possible Causes
2. Job Set-up Information
A. Referenced Information
| REFERENCE | DESIGNATION |
|---|---|
| TSM TASK 21-61-00-810-821-A | Pack 2 Electrical Component with Short Circuit (AIR PACK 2 REGUL FAULT) |
| AMM 21-61-00-710-001 | Operational Test of the Pack Temperature-Control System |
| ASM 216101 | |
| AMM 21-61-34-000-001 | Removal of the Pack Controller |
| AMM 21-61-34-000-002 | Removal of the Air-Conditioning System Controller |
| AMM 21-61-34-400-001 | Installation of the Pack Controller |
| AMM 21-61-34-400-002 | Installation of the Air-Conditioning System Controller |
| ASM 216302 |
Subtask 21-61-00-710-142-A ** ON A/C NOT FOR ALL
A. Do the operational test of the pack temperature-control system AMM 21-61-00-710-001.
Subtask 21-61-00-710-142-B ** ON A/C NOT FOR ALL 4. Fault IsolationNOTE: If a fault is detected, the PC gives a fault code for shop maintenance in addition to the related CFDS message(s) (refer to TSM chapter 21-63-00, page block 301).
Subtask 21-61-00-810-170-A ** ON A/C NOT FOR ALL
A. If the test gives the maintenance message P2 CONT:
Subtask 21-61-00-810-170-B ** ON A/C NOT FOR ALL - replace the P2 CONTROLLER [27HH] AMM 21-61-34-000-001 and AMM 21-61-34-400-001.
- do a check and repair the wiring if necessary between:
PC 2 (27HH) connector AA/5A and CB (21HH),
PC 2 (27HH) connector AA/5B and GND,
PC 2 (27HH) connector AB/13D and CB (22HH),
PC 2 (27HH) connector AB/14A and GND ASM 216101.
- a check and repair if necessary the wiring of the signal:
ARINC 429 XTR (M) from the ZC (8HK) to the PC 2 (27HH),
ARINC 429 XTR (S) from the ZC (8HK) to the PC 2 (27HH),
ARINC 429 RCV (S) from the ZC (8HK) to the PC 1 (7HH) ASM 216302.
- do the trouble shooting procedures for the pack 2 electrical component with short circuit (Ref. TSM TASK 21-61-00-810-821).
A. If the test gives the maintenance message ACSC2(57HH):
Subtask 21-61-00-710-143-A - replace the CONT-AIR COND SYSTEM 2 [57HH] AMM 21-61-34-000-002 and AMM 21-61-34-400-002.
- do the trouble shooting procedures for the pack 2 electrical component with short circuit (Ref. TSM TASK 21-61-00-810-821).
B. Do the test as given in the Para. 3.A.