Loss of Data on the Secondary ECS Bus to the EIU 1


TASK 73-25-00-810-877-A
Loss of Data on the Secondary ECS Bus to the EIU 1


1. Possible Causes
  • EIU-1 [1KS1]
  • wiring from the EIU-1 (1KS1) pins AA/3J, 3K to the first terminal block
2. Job Set-up Information
 A. Referenced Information
REFERENCE
DESIGNATION
ASM 732506
AMM 73-25-34-000-040
Removal of the Engine Interface Unit (EIU)
AMM 73-25-34-400-040
Installation of the Engine Interface Unit (EIU)
AMM 73-25-34-710-040
Operational Test of the Engine Interface Unit
AMM 73-25-34-710-043
Operational Test of the Engine Interface Unit
3. Fault Confirmation
Subtask 73-25-00-710-214-A ** ON A/C NOT FOR ALL
A. Test
Do the operational test of the engine interface unit through the CFDS AMM 73-25-34-710-040.
Subtask 73-25-00-710-214-B ** ON A/C NOT FOR ALL
A. Test
Do the operational test of the engine interface unit through the CFDS AMM 73-25-34-710-043.
4. Fault Isolation
Subtask 73-25-00-810-132-A ** ON A/C NOT FOR ALL
A. If the test gives the maintenance message EIU 1 : NO ZONE CONT S DATA:
   (1) If the fault continues:
  • do a check and repair the wiring from the EIU-1 (1KS1) pins AA/3J, 3K to the first terminal block ASM 732506.
Subtask 73-25-00-710-215-A ** ON A/C NOT FOR ALL
B. Do the test given in Para. 3.A.