Drift of the Engine 2 Bleed Transferred Pressure Transducer
TASK 36-11-00-810-956-A
Drift of the Engine 2 Bleed Transferred Pressure Transducer
1. Possible Causes
2. Job Set-up Information
A. Referenced Information
3. Fault Confirmation
Subtask 36-11-00-740-067-A ** ON A/C NOT FOR ALL
Subtask 36-11-00-865-071-A ** ON A/C NOT FOR ALL
[Rev.8 from Aug 2018]
2026.04.04 04:33:51 UTC
Drift of the Engine 2 Bleed Transferred Pressure Transducer
1. Possible Causes
2. Job Set-up Information
A. Referenced Information
| REFERENCE | DESIGNATION |
|---|---|
| TSM TASK 24-00-00-810-803-A | Circuit Breaker Tripped and/or C/B TRIPPED Warning |
| ASM 361102 | |
| AMM 36-11-15-000-001 | Removal of the Bleed Transferred Pressure-Transducer |
| AMM 36-11-15-400-001 | Installation of the Bleed Transferred Pressure-Transducer |
| AMM 36-11-34-000-001 | Removal of the BMC |
| AMM 36-11-34-400-001 | Installation of the BMC |
Subtask 36-11-00-740-067-A ** ON A/C NOT FOR ALL
A. Test
(1) Not applicable.
4. Fault Isolation(1) Not applicable.
Subtask 36-11-00-865-071-A ** ON A/C NOT FOR ALL
A. Table of the circuit breakers used in this procedure:
Subtask 36-11-00-810-250-A ** ON A/C NOT FOR ALL | PANEL | DESIGNATION | FIN | LOCATION |
|---|---|---|---|
| ** ON A/C NOT FOR ALL | |||
| 122VU | AIR BLEED/ENG 2/MONG | 2HA2 | Z22 |
B. If the fault symptom is identified by the maintenance message:
DRIFT TRANSF-PRESS XDCR 7HA2
Subtask 36-11-00-740-068-A ** ON A/C NOT FOR ALL DRIFT TRANSF-PRESS XDCR 7HA2
- Do a check of the status of the AIR BLEED/ENG 2/MONG circuit breaker (2HA2).
- Do a check for 28VDC at pin A/1 of the bleed transferred pressure transducer (7HA2) ASM 361102.
- Do a check for ground at pin A/2 of the bleed transferred pressure transducer (7HA2) ASM 361102.
- Repair the wiring between pin A/2 of the bleed transferred pressure transducer (7HA2) and the ground ASM 361102.
- Do a check of the wiring between pin A/1 of the bleed transferred pressure transducer (7HA2) and the AIR BLEED/ENG2/MONG circuit breaker (2HA2) ASM 361102.
- Repair the wiring .
- Replace the C/B-AIR BLEED/ENG 1/MONG [2HA1] ASM 361102.
- Make sure that there is a 0 psig output signal (0.9VDC) at the BMC2 (1HA2) connector between pins AA/14B and AA/15B.
- Replace the XDCR-BLEED TRANSFER PRESS, ENG 2 [7HA2] AMM 36-11-15-000-001 and AMM 36-11-15-400-001.
- Do a check and repair the wiring between pins A/3 and A/4 of the bleed transferred pressure transducer (7HA2) and pins AA/14B and AA/15B of the BMC2 (1HA2) ASM 361102.
- Replace the XDCR-BLEED TRANSFER PRESS, ENG 2 [7HA2] AMM 36-11-15-000-001 and AMM 36-11-15-400-001.
- Do the procedure (Ref. TSM TASK 24-00-00-810-803).
- Replace the C/B-AIR BLEED/ENG 1/MONG [2HA1] .
- Replace the BMC-2 [1HA2] AMM 36-11-34-000-001 and AMM 36-11-34-400-001.
C. After the subsequent flight, make sure that the fault does not continue.