Selection of the LDG FLAP 3 Position not Possible
TASK 34-48-00-810-829-A
Selection of the LDG FLAP 3 Position not Possible
1. Possible Causes
A. Referenced Information
3. Fault Confirmation
Subtask 34-48-00-710-077-A
Subtask 34-48-00-810-091-A
[Rev.8 from Aug 2018]
2026.04.04 04:33:17 UTC
Selection of the LDG FLAP 3 Position not Possible
1. Possible Causes
wiring of the GPWS/LDG FLAP 3 pushbutton switch (13WZ) - P/BSW-GPWS/LDG FLAP 3 [13WZ]
- SLAT/FLAP CONTR.COMP. [21CV]
A. Referenced Information
| REFERENCE | DESIGNATION |
|---|---|
| ESPM 2045110 | |
| AMM 27-51-34-000-001 | Removal of the SFCC |
| AMM 27-51-34-400-001 | Installation of the SFCC |
| ASM 344801 |
Subtask 34-48-00-710-077-A
A. Test
Not applicable, you cannot confirm this fault on the ground.
4. Fault IsolationNot applicable, you cannot confirm this fault on the ground.
Subtask 34-48-00-810-091-A
A. Do the procedure:
- on the GPWS section of panel 21VU:
. make sure that the GPWS/LDG FLAP 3 pushbutton switch (13WZ) is pushed (the ON legend is on)
. make sure that the GPWS/FLAP MODE pushbutton switch (7WZ) is not pushed (the OFF legend is off). - on the center pedestal, on the panel 114VU, put the flap and slat control lever in the 3 position
- make sure that there is ground at pin AB/9C of the GPWC (1WZ).
- do a check of the
wiring of the GPWS/LDG FLAP 3 pushbutton switch (13WZ) :
. pin A/B3 to GPWC (1WZ) pin AB/9C
. pin A/B1 to SFCC1 (21CV) pin AB/8K.
ASM 344801.
- repair the above wiring.
- replace the P/BSW-GPWS/LDG FLAP 3 [13WZ] ESPM 2045110.
- replace the SLAT/FLAP CONTR.COMP. [21CV] AMM 27-51-34-000-001 and AMM 27-51-34-400-001.