Loss of the ADR 1 Input Data to the IR 3
TASK 34-14-00-810-946-A
Loss of the ADR 1 Input Data to the IR 3
1. Possible Causes
A. Referenced Information
3. Fault Confirmation
Subtask 34-14-00-740-297-A 4. Fault Isolation
Subtask 34-14-00-810-200-A
[Rev.8 from Aug 2018]
2026.04.04 04:32:51 UTC
Loss of the ADR 1 Input Data to the IR 3
1. Possible Causes
- ADIRU-3 [1FP3]
wiring of the ADR INPUT 1 signal from the ADIRU 3 (1FP3) to the first terminal block
A. Referenced Information
| REFERENCE | DESIGNATION |
|---|---|
| AMM 34-12-34-000-001 | Removal of the ADIRU |
| AMM 34-12-34-400-001 | Installation of the ADIRU |
| AMM 34-14-00-740-001 | Interface Test of the IR |
| ASM 341402 |
Subtask 34-14-00-740-297-A 4. Fault Isolation
Subtask 34-14-00-810-200-A
A. If the test gives the maintenance message ADIRU1 (1FP1):
Subtask 34-14-00-740-298-A - replace the ADIRU-3 [1FP3] AMM 34-12-34-000-001 and AMM 34-12-34-400-001.
- do a check and repair the
wiring of the ADR INPUT 1 signal from the ADIRU 3 (1FP3) to the first terminal block ASM 341402.
B. Do the test given in Para. 3.