TASK 34-14-00-810-864-A
Loss of the IR 3 BUS 2 Output Identified by the EIS 2


1. Possible Causes
  • ADIRU-3 [1FP3]
  • wiring of the INERTIAL REFERENCE OUTPUT BUS 2 bus from the ADIRU 3 (1FP3) to the first terminal block
2. Job Set-up Information
 A. Referenced Information
REFERENCE
DESIGNATION
AMM 31-60-00-740-002
Perform Electronic Instrument System (EIS) Input Test
AMM 31-60-00-740-007
GROUND SCANNING Test of the DMC
AMM 34-12-34-000-001
Removal of the ADIRU
AMM 34-12-34-400-001
Installation of the ADIRU
ASM 341401
3. Fault Confirmation
Subtask 34-14-00-740-154-A ** ON A/C NOT FOR ALL
A. Test
Do the EIS input test (system 2) AMM 31-60-00-740-002.
Subtask 34-14-00-740-154-B ** ON A/C NOT FOR ALL
A. Test
Do the Ground Scanning Test of the DMC (system 2) AMM 31-60-00-740-007.
4. Fault Isolation
Subtask 34-14-00-810-113-A ** ON A/C NOT FOR ALL
A. If the test gives the maintenance message DMC2 : NO IRS3 DATA:
   (1) If the fault continues:
  • do a check and repair the wiring of the INERTIAL REFERENCE OUTPUT BUS 2 bus from the ADIRU 3 (1FP3) to the first terminal block ASM 341401.
Subtask 34-14-00-810-113-B ** ON A/C NOT FOR ALL
A. If the test gives the maintenance message ADIRU3(1FP3)BUSX IR/DMC2(1WT2)
   (1) If the fault continues:
  • do a check and repair the wiring of the INERTIAL REFERENCE OUTPUT BUS 2 bus from the ADIRU 3 (1FP3) to the first terminal block ASM 341401.
Subtask 34-14-00-740-155-A
B. Do the test given in Para. 3.