Loss of the IR 2 BUS 3 Output Identified by the AFS
TASK 34-14-00-810-838-A
Loss of the IR 2 BUS 3 Output Identified by the AFS
1. Possible Causes
A. Referenced Information
3. Fault Confirmation
Subtask 34-14-00-710-060-A 4. Fault Isolation
Subtask 34-14-00-810-087-A
[Rev.8 from Aug 2018]
2026.04.04 04:32:45 UTC
Loss of the IR 2 BUS 3 Output Identified by the AFS
1. Possible Causes
- ADIRU-2 [1FP2]
wiring of the INERTIAL REFERENCE OUTPUT BUS 3 bus from the ADIRU 2 (1FP2) to the first terminal block
A. Referenced Information
| REFERENCE | DESIGNATION |
|---|---|
| AMM 22-91-00-710-001 | Ground Scanning of the AFS |
| AMM 34-12-34-000-001 | Removal of the ADIRU |
| AMM 34-12-34-400-001 | Installation of the ADIRU |
| ASM 341401 |
Subtask 34-14-00-710-060-A 4. Fault Isolation
Subtask 34-14-00-810-087-A
A. If the test gives the maintenance message AFS : ADIRU 2:
Subtask 34-14-00-710-061-A - replace the ADIRU-2 [1FP2] AMM 34-12-34-000-001 and AMM 34-12-34-400-001.
- do a check and repair the
wiring of the INERTIAL REFERENCE OUTPUT BUS 3 bus from the ADIRU 2 (1FP2) to the first terminal block ASM 341401.
B. Do the test given in Para. 3.