Loss of the ADR2 BUS3 Output Identified by the EFCS1
TASK 34-13-81-810-805-A
Loss of the ADR2 BUS3 Output Identified by the EFCS1
1. Possible Causes
A. Referenced Information
3. Fault Confirmation
Subtask 34-13-81-740-058-A 4. Fault Isolation
Subtask 34-13-81-810-054-A
[Rev.8 from Aug 2018]
2026.04.04 04:32:33 UTC
Loss of the ADR2 BUS3 Output Identified by the EFCS1
1. Possible Causes
- ADIRU-2 [1FP2]
wiring of the ADR OUTPUT BUS3 bus from the ADIRU2 (1FP2) to the first terminal block - wiring between the terminal blocks 1510VT and 1851VT
A. Referenced Information
| REFERENCE | DESIGNATION |
|---|---|
| AMM 27-96-00-740-001 | BITE Test of the EFCS (Ground Scanning) |
| AWM 341122 | |
| AMM 34-12-34-000-001 | Removal of the ADIRU |
| AMM 34-12-34-400-001 | Installation of the ADIRU |
| ASM 341301 | |
| AMM 34-14-00-740-001 | Interface Test of the IR |
Subtask 34-13-81-740-058-A 4. Fault Isolation
Subtask 34-13-81-810-054-A
A. If the test gives the maintenance message ADR2 OR BUS3 TO ELAC1:
Subtask 34-13-81-740-059-A - do the interface test of the IR (system 1) AMM 34-14-00-740-001.
- replace the ADIRU-2 [1FP2] AMM 34-12-34-000-001 and AMM 34-12-34-400-001.
- do a check and repair the
wiring of the ADR OUTPUT BUS3 bus from the ADIRU2 (1FP2) to the first terminal block ASM 341301.
- do a check and repair the wiring between the terminal blocks 1510VT and 1851VT between pins 1U, 1V and 4E, 3E AWM 341122.
B. Do the test given in Para. 3.