Loss of the ADR 1 BUS 4 Output Identified by the CFDS
TASK 34-13-00-810-840-A
Loss of the ADR 1 BUS 4 Output Identified by the CFDS
1. Possible Causes
A. Referenced Information
3. Fault Confirmation
Subtask 34-13-00-865-051-A
Subtask 34-13-00-810-089-A
[Rev.8 from Aug 2018]
2026.04.04 04:32:24 UTC
Loss of the ADR 1 BUS 4 Output Identified by the CFDS
1. Possible Causes
- ADIRU-1 [1FP1]
wiring of the ADR OUTPUT BUS 4 bus from the ADIRU 1 (1FP1) to the first terminal block
A. Referenced Information
| REFERENCE | DESIGNATION |
|---|---|
| AMM 31-32-00-869-002 | Procedure for the Class 3 Fault Reading |
| AMM 34-12-34-000-001 | Removal of the ADIRU |
| AMM 34-12-34-400-001 | Installation of the ADIRU |
| ASM 341301 |
Subtask 34-13-00-865-051-A
A. Make sure that this(these) circuit breaker(s) is(are) closed:
Subtask 34-13-00-740-095-A 4. Fault Isolation| PANEL | DESIGNATION | FIN | LOCATION |
|---|---|---|---|
| ** ON A/C ALL | |||
| 49VU | NAV PROBES/ADIRU 1/AND AOA 1/26VAC | 5FP1 | F07 |
| 49VU | NAV PROBES/ADIRU1/115VAC | 4FP1 | F06 |
| 105VU | ADIRS/ADIRU1/28VDC | 6FP1 | C02 |
Subtask 34-13-00-810-089-A
A. If the test gives the maintenance message NO ADR1 DATA:
Subtask 34-13-00-740-096-A - replace the ADIRU-1 [1FP1] , AMM 34-12-34-000-001 and AMM 34-12-34-400-001.
- do a check and repair the
wiring of the ADR OUTPUT BUS 4 bus from the ADIRU 1 (1FP1) to the first terminal block , ASM 341301.
B. Do the test given in Para. 3.B.