Loss of the ADR 1 BUS 3 Output Identified by the ECAM 1


TASK 34-13-00-810-828-A
Loss of the ADR 1 BUS 3 Output Identified by the ECAM 1


1. Possible Causes
  • ADIRU-1 [1FP1]
  • wiring of the ADR OUTPUT BUS 3 bus from the ADIRU 1 (1FP1) to the first terminal block
2. Job Set-up Information
 A. Referenced Information
REFERENCE
DESIGNATION
AMM 31-50-00-710-001
Ground Scanning of the Central Warning System
AMM 34-12-34-000-001
Removal of the ADIRU
AMM 34-12-34-400-001
Installation of the ADIRU
ASM 341301
3. Fault Confirmation
Subtask 34-13-00-710-074-A
A. Test
Do the operational test of the central warning systems (system 1) AMM 31-50-00-710-001.
4. Fault Isolation
Subtask 34-13-00-810-077-A
A. If the test gives the maintenance message FWC1 : NO DATA FROM ADC1:
   (1) If the fault continues:
  • do a check and repair the wiring of the ADR OUTPUT BUS 3 bus from the ADIRU 1 (1FP1) to the first terminal block, ASM 341301.
Subtask 34-13-00-710-075-A
B. Do the test given in Para. 3.
[Rev.8 from Aug 2018] 2026.04.04 04:32:22 UTC