Loss of the CIDS1 Bus of the SDAC 2
TASK 31-54-00-810-966-A
Loss of the CIDS1 Bus of the SDAC 2
1. Possible Causes
A. Referenced Information
3. Fault Confirmation
Subtask 31-54-00-865-153-A
Subtask 31-54-00-810-216-A
[Rev.8 from Aug 2018]
2026.04.04 04:30:35 UTC
Loss of the CIDS1 Bus of the SDAC 2
1. Possible Causes
- SDAC-2 [1WV2]
- wiring
A. Referenced Information
| REFERENCE | DESIGNATION |
|---|---|
| ASM 237302 | |
| AWM 237310 | |
| AMM 31-50-00-710-001 | Ground Scanning of the Central Warning System |
| AMM 31-55-34-000-001 | Removal of the SDAC |
| AMM 31-55-34-400-001 | Installation of the SDAC |
Subtask 31-54-00-865-153-A
A. Make sure that this(these) circuit breaker(s) is(are) closed:
Subtask 31-54-00-710-363-A 4. Fault Isolation| PANEL | DESIGNATION | FIN | LOCATION |
|---|---|---|---|
| ** ON A/C ALL | |||
| 49VU | COM/CIDS/DIR ESS/1 | 150RH | G01 |
| ** ON A/C NOT FOR ALL | |||
| 121VU | COM/CIDS/DIR 1/BAT | 147RH | P13 |
| 121VU | COM/CIDS/BAT/CTL | 148RH | P12 |
| ** ON A/C NOT FOR ALL | |||
| 121VU | COM NAV/CIDS/DIR NORM/1 | 151RH | M05 |
| ** ON A/C NOT FOR ALL | |||
| 121VU | COM NAV/CIDS/DIR NORM/1 | 151RH | M06 |
Subtask 31-54-00-810-216-A
A. If the test gives the maintenance message
SDAC2:NO DATA FROM CIDS1:
Subtask 31-54-00-710-364-A SDAC2:NO DATA FROM CIDS1:
- replace the SDAC-2 [1WV2] , AMM 31-55-34-000-001 and AMM 31-55-34-400-001.
- do a check and repair the wiring from the SDAC 2 (1WV2) pins AB/08E, 08F to the first terminal block, AWM 237310 and ASM 237302.
B. Do the test given in Para. 3.