W DOC AIRBUS | TSM A320F

Loss of the ESS TRU VOLTAGE Input of the SDAC 2


TASK 31-54-00-810-882-A
Loss of the ESS TRU VOLTAGE Input of the SDAC 2


1. Possible Causes
  • SDAC-2 [1WV2]
  • wiring
2. Job Set-up Information
 A. Referenced Information
REFERENCE
DESIGNATION
ASM 243401
AMM 31-50-00-710-001
Ground Scanning of the Central Warning System
AMM 31-55-34-000-001
Removal of the SDAC
AMM 31-55-34-400-001
Installation of the SDAC
3. Fault Confirmation
Subtask 31-54-00-865-110-A
A. Make sure that this(these) circuit breaker(s) is(are) closed:
PANELDESIGNATIONFINLOCATION
** ON A/C ALL
106VUESS TR/SPLY4PEC01
Subtask 31-54-00-710-200-A
B. Test
Do the ground scanning of the central warning systems AMM 31-50-00-710-001.
4. Fault Isolation
Subtask 31-54-00-810-131-A
A. If the test gives the maintenance message SDAC 2 : NO TR ESS VOLTAGE 1PE:
   (1) If the fault continues:
  • do a check and repair the wiring from the SDAC 2 (1WV2) pin AB/7K to the first terminal block , ASM 243401.
Subtask 31-54-00-710-201-A
B. Do the test given in Para. 3.B.
[Rev.8 from Aug 2018] 2026.04.04 04:30:29 UTC