Failure of the SDAC 2
TASK 31-54-00-810-803-A
Failure of the SDAC 2
1. Possible Causes
A. Referenced Information
3. Fault Confirmation
Subtask 31-54-00-710-054-A 4. Fault Isolation
Subtask 31-54-00-865-143-A
[Rev.8 from Aug 2018]
2026.04.04 04:40:41 UTC
Failure of the SDAC 2
1. Possible Causes
- SDAC-2 [1WV2]
wiring from the SDAC 2 (1WV2) pin AC/1 to the circuit breaker (2WV) - C/B-EIS/SDAC/2/SPLY [2WV]
A. Referenced Information
| REFERENCE | DESIGNATION |
|---|---|
| AMM 31-50-00-710-001 | Ground Scanning of the Central Warning System |
| ASM 315101 | |
| AMM 31-55-34-000-001 | Removal of the SDAC |
| AMM 31-55-34-400-001 | Installation of the SDAC |
Subtask 31-54-00-710-054-A 4. Fault Isolation
Subtask 31-54-00-865-143-A
A. Table of the circuit breakers used in this procedure:
Subtask 31-54-00-810-058-A | PANEL | DESIGNATION | FIN | LOCATION |
|---|---|---|---|
| ** ON A/C ALL | |||
| 121VU | EIS/SDAC/2/SPLY | 2WV | Q06 |
B. If the test gives the maintenance message:
SDAC2
Subtask 31-54-00-710-055-A SDAC2
- do a check of the status of the circuit breaker (2WV).
- replace the SDAC-2 [1WV2] , AMM 31-55-34-000-001 and AMM 31-55-34-400-001.
- do a check of the
wiring from the SDAC 2 (1WV2) pin AC/1 to the circuit breaker (2WV) , ASM 315101.
- repair the wiring given above.
- replace the C/B-EIS/SDAC/2/SPLY [2WV] .
- close the circuit breaker.
- replace the SDAC-2 [1WV2] .
- do a check and repair for a short to ground the wiring between the circuit breaker (2WV) and the SDAC 2 (1WV2).
- replace the SDAC-2 [1WV2] .
C. Do the test given in Para. 3.