DMU Receives No Data from the PC 1 (ACSC 1)


TASK 31-36-00-810-927-A
DMU Receives No Data from the PC 1 (ACSC 1)


1. Possible Causes
2. Job Set-up Information
 A. Referenced Information
REFERENCE
DESIGNATION
AMM 21-61-00-710-001
Operational Test of the Pack Temperature-Control System
AMM 31-36-00-710-001
Test of the DMU
AMM 31-36-34-000-001
Removal of the Data Management Unit (DMU)
AMM 31-36-34-400-001
Installation of the Data Management Unit (DMU)
ASM 313701
3. Fault Confirmation
Subtask 31-36-00-740-217-A ** ON A/C NOT FOR ALL
A. Do the DMU (1TV) fault monitoring test AMM 31-36-00-710-001.
NOTE: Make sure that the circuit breakers 1TV on the panel 121VU and 1HH, 2HH, 3HH and 4HH on the panel 122VU are closed during the test.
4. Fault Isolation
Subtask 31-36-00-810-141-A ** ON A/C NOT FOR ALL
A. If the test gives the maintenance message:

  • ACSC 1 (47HH) / DMU (1TV)

   (1) Do the operational test of the Pack Temperature-Control System AMM 21-61-00-710-001.

     (a) If the test gives a different maintenance message, you can find the related trouble shooting procedure in the applicable Page Block 201.

   (2) If the fault continues:
  • do a check and repair the wiring from the [47HH] to the DMU [1TV] ASM 313701:

    ACSC 1 Connector AB/11B to DMU Connector AA/2C
    ACSC 1 Connector AB/11C to DMU Connector AA/2D.

   (3) If the fault continues:
Subtask 31-36-00-740-218-A ** ON A/C NOT FOR ALL
B. Do the test given in Para. 3.