FDIMU Receives No Data from the SDAC 1 or SDAC 2
TASK 31-36-00-810-915-A
FDIMU Receives No Data from the SDAC 1 or SDAC 2
1. Possible Causes
2. Job Set-up Information
A. Referenced Information
3. Fault Confirmation
Subtask 31-36-00-865-051-A ** ON A/C NOT FOR ALL
Subtask 31-36-00-810-129-A ** ON A/C NOT FOR ALL
[Rev.8 from Aug 2018]
2026.04.04 04:30:07 UTC
FDIMU Receives No Data from the SDAC 1 or SDAC 2
1. Possible Causes
2. Job Set-up Information
A. Referenced Information
| REFERENCE | DESIGNATION |
|---|---|
| AMM 31-36-00-740-012 | Test of the Flight Data Interface and Management Unit (FDIMU) |
| AMM 31-36-34-000-002 | Removal of the FDIU/DMU (FDIMU) |
| AMM 31-36-34-400-002 | Installation of the FDIU/DMU (FDIMU) |
| ASM 313701 | |
| AMM 31-50-00-710-001 | Ground Scanning of the Central Warning System |
Subtask 31-36-00-865-051-A ** ON A/C NOT FOR ALL
A. Make sure that this(these) circuit breaker(s) is(are) closed:
Subtask 31-36-00-740-202-A ** ON A/C NOT FOR ALL 4. Fault Isolation| PANEL | DESIGNATION | FIN | LOCATION |
|---|---|---|---|
| ** ON A/C NOT FOR ALL | |||
| 49VU | SDAC/1 AND 2/28VDC/ESS BUS | 12WV | F05 |
| 49VU | SDAC/1/SPLY | 3WV | F04 |
| 49VU | SDAC/2/26VAC SYNC/AC ESS BUS | 6WV | F03 |
| 49VU | SDAC/1/26VAC SYNC/AC ESS BUS | 5WV | F02 |
| ** ON A/C NOT FOR ALL | |||
| 121VU | EIS/SDAC/1/BUS1/26VAC SYNC AC | 9WV | Q04 |
| ** ON A/C NOT FOR ALL | |||
| 121VU | AIDS & RCDR/FDIMU | 5TV | K15 |
| 121VU | HYDRAULIC/HYD/QTY/IND | 1831GQ | P35 |
| 121VU | EIS/SDAC/2/SPLY | 2WV | Q06 |
| 121VU | EIS/SDAC/2/BUS1/26VAC SYNC AC | 10WV | Q05 |
| 121VU | EIS/SDAC/1/BUS2/26VAC SYNC AC | 7WV | Q03 |
| 121VU | EIS/SDAC/2/BUS2/26VAC SYNC AC | 8WV | Q02 |
Subtask 31-36-00-810-129-A ** ON A/C NOT FOR ALL
A. If the test gives the maintenance message:
(a) If the test gives a different maintenance message, you can find the related trouble shooting procedure in the applicable Page Block 201.
(2) If the fault continues:
Subtask 31-36-00-740-203-A ** ON A/C NOT FOR ALL - SDAC1 (1WV1) / FDIMU (10TV) or
- SDAC2 (1WV2) / FDIMU (10TV)
(a) If the test gives a different maintenance message, you can find the related trouble shooting procedure in the applicable Page Block 201.
(2) If the fault continues:
- do a check and if necessary repair the wiring between the SDAC-1 [1WV1] or SDAC-2 [1WV2] and the DMU/FDIU (FDIMU) [10TV] ASM 313701:
SDAC 1 Connector AB/8J to FDIMU Connector AA/6G
SDAC 1 Connector AB/8K to FDIMU Connector AA/6H
or
SDAC 2 Connector AB/8J to FDIMU Connector AB/6G
SDAC 2 Connector AB/8K to FDIMU Connector AB/6H
- replace the FDIMU (10TV) AMM 31-36-34-000-002 and AMM 31-36-34-400-002.
B. Do the test given in Para. 3.