DMU Receives No Data from the FCDC 1 or FCDC 2
TASK 31-36-00-810-824-A
DMU Receives No Data from the FCDC 1 or FCDC 2
1. Possible Causes
2. Job Set-up Information
A. Referenced Information
3. Fault Confirmation
Subtask 31-36-00-740-074-A ** ON A/C NOT FOR ALL
Subtask 31-36-00-810-064-A ** ON A/C NOT FOR ALL
[Rev.8 from Aug 2018]
2026.04.04 04:30:03 UTC
DMU Receives No Data from the FCDC 1 or FCDC 2
1. Possible Causes
2. Job Set-up Information
A. Referenced Information
| REFERENCE | DESIGNATION |
|---|---|
| AMM 27-96-00-710-001 | Operational Test of the FCDC |
| AMM 31-36-00-710-001 | Test of the DMU |
| AMM 31-36-34-000-001 | Removal of the Data Management Unit (DMU) |
| AMM 31-36-34-400-001 | Installation of the Data Management Unit (DMU) |
| ASM 313701 |
Subtask 31-36-00-740-074-A ** ON A/C NOT FOR ALL
A. Do the DMU (1TV) fault monitoring test AMM 31-36-00-710-001.
4. Fault IsolationNOTE: Make sure that the circuit breakers 1TV, 20CE2 on the panel 121VU and 20CE1 on the panel 49VU are closed during the test.
Subtask 31-36-00-810-064-A ** ON A/C NOT FOR ALL
A. If the test gives the maintenance message:
(a) If the test gives a different maintenance message, you can find the related trouble shooting procedure in the applicable Page Block 201.
(2) If the fault continues:
Subtask 31-36-00-740-075-A ** ON A/C NOT FOR ALL - NO FCDC 1 DATA, or
- NO FCDC 2 DATA
(a) If the test gives a different maintenance message, you can find the related trouble shooting procedure in the applicable Page Block 201.
(2) If the fault continues:
- do a check and repair the wiring from the FCDC-1 [3CE1] or FCDC-2 [3CE2] to the DMU [1TV] ASM 313701:
FCDC 1 Connector AA/5E to DMU Connector AA/3C
FCDC 1 Connector AA/5F to DMU Connector AA/3D
or
FCDC 2 Connector AB/5E to DMU Connector AB/3C
FCDC 2 Connector AB/5F to DMU Connector AB/3D
- replace the DMU (1TV) AMM 31-36-34-000-001 and AMM 31-36-34-400-001.
B. Do the test given in Para. 3.