TASK 31-33-00-810-823-A
DMU receives no Data from the FDIU
1. Possible Causes
2. Job Set-up Information
A. Referenced Information
3. Fault Confirmation
Subtask 31-33-00-710-064-A ** ON A/C NOT FOR ALL
Subtask 31-33-00-810-057-A ** ON A/C NOT FOR ALL
[Rev.8 from Aug 2018]
2026.04.04 04:30:01 UTC
DMU receives no Data from the FDIU
1. Possible Causes
2. Job Set-up Information
A. Referenced Information
| REFERENCE | DESIGNATION |
|---|---|
| AMM 31-33-00-710-006 | Operational Check of DFDR via MCDU |
| ASM 313301 | |
| AMM 31-36-00-710-001 | Test of the DMU |
| AMM 31-36-34-000-001 | Removal of the Data Management Unit (DMU) |
| AMM 31-36-34-400-001 | Installation of the Data Management Unit (DMU) |
Subtask 31-33-00-710-064-A ** ON A/C NOT FOR ALL
A. Do the test of the DMU AMM 31-36-00-710-001
4. Fault IsolationNOTE: make sure that the circuit breakers 7TU and 4TV are closed.
Subtask 31-33-00-810-057-A ** ON A/C NOT FOR ALL
A. If the test gives the maintenace message NO FDIU DATA:
(2) If the fault continues:
Subtask 31-33-00-710-065-A ** ON A/C NOT FOR ALL - do the FDIU (2TU) fault monitoring test via the MCDU AMM 31-33-00-710-006
(2) If the fault continues:
- replace the DMU [1TV] AMM 31-36-34-000-001 and AMM 31-36-34-400-001
- do a check and repair the wiring between:
FDIU [2TU] AB/9J and DMU [1TV] AA/5E,
FDIU [2TU] AB/9K and DMU [1TV] AA5F ASM 313301.
B. Do the test as given in Para. 3 again to check the correct operation
(no maintenace message display).
(no maintenace message display).