Loss of the ARINC 429 Data between the FWC 2 and the CFDIU
TASK 31-32-00-810-916-A
Loss of the ARINC 429 Data between the FWC 2 and the CFDIU
1. Possible Causes
A. Referenced Information
3. Fault Confirmation
Subtask 31-32-00-865-156-A
Subtask 31-32-00-810-165-A
[Rev.8 from Aug 2018]
2026.04.04 04:29:57 UTC
Loss of the ARINC 429 Data between the FWC 2 and the CFDIU
1. Possible Causes
- CFDIU [1TW]
- wiring
A. Referenced Information
| REFERENCE | DESIGNATION |
|---|---|
| AMM 31-32-00-869-002 | Procedure for the Class 3 Fault Reading |
| AMM 31-32-34-000-001 | Removal of the CFDIU |
| AMM 31-32-34-400-001 | Installation of the CFDIU |
| ASM 315205 |
Subtask 31-32-00-865-156-A
A. Make sure that this(these) circuit breaker(s) is(are) closed:
Subtask 31-32-00-740-276-A 4. Fault Isolation| PANEL | DESIGNATION | FIN | LOCATION |
|---|---|---|---|
| ** ON A/C ALL | |||
| 121VU | EIS/FWC2/SPLY | 2WW | Q07 |
Subtask 31-32-00-810-165-A
A. If the test gives the maintenance message NO FWC 2 DATA:
Subtask 31-32-00-740-277-A - replace the CFDIU [1TW] AMM 31-32-34-000-001 and AMM 31-32-34-400-001.
- do a check and repair the wiring from the CFDIU (1TW) pins AB/5F, 5G to the first terminal block ASM 315205.
B. Do the test given in Para. 3.B.