Loss of the ARINC 429 Data between the FWC 1 and the CFDIU


TASK 31-32-00-810-915-A
Loss of the ARINC 429 Data between the FWC 1 and the CFDIU


1. Possible Causes
  • CFDIU [1TW]
  • wiring
2. Job Set-up Information
 A. Referenced Information
REFERENCE
DESIGNATION
AMM 31-32-00-740-003
Ground Scanning of the CFDIU
AMM 31-32-00-869-002
Procedure for the Class 3 Fault Reading
AMM 31-32-34-000-001
Removal of the CFDIU
AMM 31-32-34-400-001
Installation of the CFDIU
ASM 315205
3. Fault Confirmation
Subtask 31-32-00-865-140-A
A. Make sure that this(these) circuit breaker(s) is(are) closed:
PANELDESIGNATIONFINLOCATION
** ON A/C ALL
49VUFWS/FWC1/SPLY3WWF01
Subtask 31-32-00-740-232-A
B. Test
On the CFDS MENU page, get access to the AVIONICS STATUS page AMM 31-32-00-869-002.
If the fault is not confirmed, do the GROUND SCANNING of the CFDIU AMM 31-32-00-740-003.
4. Fault Isolation
Subtask 31-32-00-810-143-A
A. If the test gives the maintenance message:
NO FWC 1 DATA
   (1) If the fault continues:
  • do a check and repair the wiring from the CFDIU (1TW) pins AA/5D, 5E to the first terminal block , ASM 315205.
Subtask 31-32-00-740-233-A
B. Do the test given in Para. 3.B.