Loss of the PHC 3 Output Bus by the CFDIU


TASK 31-32-00-810-896-A
Loss of the PHC 3 Output Bus by the CFDIU


1. Possible Causes
  • CFDIU [1TW]
  • PHC-3 [6DA3]
  • wiring from the CFDIU (1TW) to the PHC 3 (6DA3)
2. Job Set-up Information
 A. Referenced Information
REFERENCE
DESIGNATION
AMM 30-31-34-000-002
Removal of the Probe Heat Computer (PHC)
AMM 30-31-34-400-002
Installation of the Probe Heat Computer (PHC)
AMM 31-32-00-869-002
Procedure for the Class 3 Fault Reading
ASM 313206
AMM 31-32-34-000-001
Removal of the CFDIU
AMM 31-32-34-400-001
Installation of the CFDIU
3. Fault Confirmation
Subtask 31-32-00-865-143-A
A. Make sure that this(these) circuit breaker(s) is(are) closed:
PANELDESIGNATIONFINLOCATION
** ON A/C ALL
122VUANTI ICE/PROBES/PHC/32DA3Y16
122VUANTI ICE/PROBES/3/PITOT3DA3Z16
122VUANTI ICE/PROBES/3/AOA4DA3Z15
122VUANTI ICE/PROBES/3/STATIC5DA3Z14
Subtask 31-32-00-740-238-A
B. Test
On the CFDS MENU page, get access to the AVIONICS STATUS page AMM 31-32-00-869-002.
4. Fault Isolation
Subtask 31-32-00-810-146-A
A. If the test gives the maintenance message NO PHC3 DATA:
   (1) If the fault continues:
   (2) If the fault continues:
  • do a check and repair the wiring from the CFDIU (1TW) to the PHC 3 (6DA3) from pins AB/2F, 2G to pins A/M, N ASM 313206.
Subtask 31-32-00-740-239-A
B. Do the test given in Para. 3.B.