Loss of the Output Bus from the CIDS Director 2 to the CFDIU


TASK 31-32-00-810-889-A
Loss of the Output Bus from the CIDS Director 2 to the CFDIU


1. Possible Causes
  • DIR-CIDS, 1 [101RH]
  • DIR-CIDS, 2 [102RH]
  • CFDIU [1TW]
  • wiring from the CFDIU (1TW) to the CIDS director 2 (102RH)
  • wiring
2. Job Set-up Information
 A. Referenced Information
REFERENCE
DESIGNATION
AMM 23-73-34-000-001
Removal of the CIDS Director
AMM 23-73-34-400-001
Installation of the CIDS Director
AMM 31-32-00-740-009
Read the AVIONICS STATUS on the MCDU
ASM 313205
AMM 31-32-34-000-001
Removal of the CFDIU
AMM 31-32-34-400-001
Installation of the CFDIU
3. Fault Confirmation
Subtask 31-32-00-865-135-A
A. Make sure that this(these) circuit breaker(s) is(are) closed:
PANELDESIGNATIONFINLOCATION
** ON A/C ALL
49VUCOM/CIDS/DIR ESS/1150RHG01
** ON A/C NOT FOR ALL
121VUCOM NAV/CIDS/DIR NORM/1151RHM05
** ON A/C NOT FOR ALL
121VUCOM NAV/CIDS/DIR NORM/1151RHM06
Subtask 31-32-00-740-222-A ** ON A/C NOT FOR ALL
B. Test
   (1) Read the AVIONICS STATUS on the MCDU AMM 31-32-00-740-009.
Subtask 31-32-00-740-222-B ** ON A/C NOT FOR ALL
B. Test
   (1) Read the AVIONICS STATUS on the MCDU AMM 31-32-00-740-009.
   (2) Make sure that there is no INOP SYS, no MAINTENANCE STATUS or no ECAM warning related to the NO CIDS 2 DATA maintenance message.
4. Fault Isolation
Subtask 31-32-00-810-138-A ** ON A/C NOT FOR ALL
A. If the test gives the maintenance message NO CIDS 2 DATA:
   (1) If the fault continues:
     (a) If the fault continues:
  • do a check and repair the wiring from the CFDIU (1TW) to the CIDS director 2 (102RH) from pins AB/3D, 3E to pins AA/11A, 11B
  • do a check and repair the wiring from the CFDIU (1TW) to the CIDS director 2 (102RH) from pins AB/11D, 11E to pins AA/11D, 11E
    ASM 313205.
   (2) If the test gives the maintenance message NO CIDS 1 DATA:
  • replace the CIDS that you installed on side 1.
Subtask 31-32-00-810-138-B ** ON A/C NOT FOR ALL
A. If the test gives the maintenance message NO CIDS 2 DATA:
   (1) If the fault continues:
     (a) If the fault continues:
  • do a check and repair the wiring from the CFDIU (1TW) to the CIDS director 2 (102RH) from pins AB/3D, 3E to pins AA/11A, 11B
  • do a check and repair the wiring from the CFDIU (1TW) to the CIDS director 2 (102RH) from pins AB/11D, 11E to pins AA/11D, 11E
    ASM 313205.
   (2) If the test gives the maintenance message NO CIDS 1 DATA:
  • replace the CIDS that you installed on side 1.
Subtask 31-32-00-740-223-A
B. Do the test given in Para. 3.B.