Loss of the Output Bus from the ACSC2 or the Zone Temperature Controller to the CFDIU
TASK 31-32-00-810-885-A
Loss of the Output Bus from the ACSC2 or the Zone Temperature Controller to the CFDIU
1. Possible Causes
A. Referenced Information
3. Fault Confirmation
Subtask 31-32-00-740-214-A 4. Fault Isolation
Subtask 31-32-00-810-134-A
[Rev.8 from Aug 2018]
2026.04.04 04:29:54 UTC
Loss of the Output Bus from the ACSC2 or the Zone Temperature Controller to the CFDIU
1. Possible Causes
- CFDIU [1TW]
- wiring
A. Referenced Information
| REFERENCE | DESIGNATION |
|---|---|
| AMM 31-32-00-740-009 | Read the AVIONICS STATUS on the MCDU |
| ASM 313205 | |
| AMM 31-32-34-000-001 | Removal of the CFDIU |
| AMM 31-32-34-400-001 | Installation of the CFDIU |
Subtask 31-32-00-740-214-A 4. Fault Isolation
Subtask 31-32-00-810-134-A
A. If the test gives the maintenance message NO ZONE CTL DATA or NO ACSC2 DATA:
Subtask 31-32-00-740-215-A - replace the CFDIU [1TW] AMM 31-32-34-000-001 and AMM 31-32-34-400-001.
- do a check and repair the wiring from the CFDIU (1TW) pins AB/2B, 2C to the first terminal block ASM 313205.
B. Do the test given in Para. 3.