Loss of the Bus Output from the GPWC Computer to the CFDIU


TASK 31-32-00-810-843-A
Loss of the Bus Output from the GPWC Computer to the CFDIU


1. Possible Causes
  • CFDIU [1TW]
  • GPWC [1WZ]
  • wiring from the CFDIU (1TW) to the GPWC (1WZ)
2. Job Set-up Information
 A. Referenced Information
REFERENCE
DESIGNATION
AMM 31-32-00-869-002
Procedure for the Class 3 Fault Reading
ASM 313205
AMM 31-32-34-000-001
Removal of the CFDIU
AMM 31-32-34-400-001
Installation of the CFDIU
AMM 34-48-34-000-001
Removal of the GPWC
AMM 34-48-34-400-001
Installation of the GPWC
3. Fault Confirmation
Subtask 31-32-00-865-090-A
A. Make sure that this(these) circuit breaker(s) is(are) closed:
PANELDESIGNATIONFINLOCATION
** ON A/C ALL
121VUEIS/GPWS/115VAC3WZP07
121VUEIS/GPWS/28VDC2WZP06
Subtask 31-32-00-740-132-A
B. Test
On the CFDS MENU page, get access to the AVIONICS STATUS page AMM 31-32-00-869-002.
4. Fault Isolation
Subtask 31-32-00-810-091-A
A. If the test gives the maintenance message NO GPWC DATA:
   (1) If the fault continues:
     (a) If the fault continues:
  • do a check and repair the wiring from the CFDIU (1TW) to the GPWC (1WZ) from pins AA/10H, 10J to pins AB/1C, 1D , ASM 313205.
Subtask 31-32-00-740-133-A
B. Do the test given in Para. 3.B.