W DOC AIRBUS | TSM A320F

Loss of the Bus Output from the FQIC to the CFDIU


TASK 31-32-00-810-821-A
Loss of the Bus Output from the FQIC to the CFDIU


1. Possible Causes
  • CFDIU [1TW]
  • FQIC [3QT]
  • wiring from the CFDIU (1TW) to the FQIC (3QT)
2. Job Set-up Information
 A. Referenced Information
REFERENCE
DESIGNATION
AMM 28-42-34-000-001
Removal of the Fuel Quantity-Indicating Computer (FQIC)
AMM 28-42-34-400-001
Installation of the Fuel Quantity-Indicating Computer (FQIC)
AMM 31-32-00-869-002
Procedure for the Class 3 Fault Reading
ASM 313204
AMM 31-32-34-000-001
Removal of the CFDIU
AMM 31-32-34-400-001
Installation of the CFDIU
3. Fault Confirmation
Subtask 31-32-00-865-068-A
A. Make sure that this(these) circuit breaker(s) is(are) closed:
PANELDESIGNATIONFINLOCATION
** ON A/C ALL
49VUFUEL/FQI/CHAN/11QTA13
121VUFUEL/FQI/CHANNEL/1 AND 28QTL26
121VUFUEL/FQI/CHAN/22QTM27
Subtask 31-32-00-740-088-A
B. Test
On the CFDS MENU page, get access to the AVIONICS STATUS page AMM 31-32-00-869-002.
4. Fault Isolation
Subtask 31-32-00-810-069-A ** ON A/C NOT FOR ALL
A. If the test gives the maintenance message NO FQI DATA:
   (1) If the fault continues:
     (a) If the fault continues:
  • do a check and repair the wiring from the CFDIU (1TW) to the FQIC (3QT) from pins AA/5F, 5G to pins AB/12F, 13F , ASM 313204.
Subtask 31-32-00-810-069-B ** ON A/C NOT FOR ALL
A. If the test gives the maintenance message NO FQI DATA:
   (1) If the fault continues:
     (a) If the fault continues:
  • do a check and repair the wiring from the CFDIU (1TW) to the FQIC (3QT) from pins AA/5F, 5G to pins AB/8E, 8F ASM 313204.
Subtask 31-32-00-740-089-A
B. Do the test given in Para. 3.B.