Loss of the Bus Output from the FDU of the APU to the CFDIU


TASK 31-32-00-810-816-A
Loss of the Bus Output from the FDU of the APU to the CFDIU


1. Possible Causes
  • FDU-APU [13WG]
  • CFDIU [1TW]
  • wiring from CFDIU (1TW) to the FDU of the APU (13WG)
2. Job Set-up Information
 A. Referenced Information
REFERENCE
DESIGNATION
AMM 26-13-34-000-001
Removal of the APU Fire-Detection Unit (FDU)
AMM 26-13-34-400-001
Installation of the APU Fire-Detection Unit (FDU)
AMM 31-32-00-869-002
Procedure for the Class 3 Fault Reading
ASM 313206
AMM 31-32-34-000-001
Removal of the CFDIU
AMM 31-32-34-400-001
Installation of the CFDIU
3. Fault Confirmation
Subtask 31-32-00-865-063-A
A. Make sure that this(these) circuit breaker(s) is(are) closed:
PANELDESIGNATIONFINLOCATION
** ON A/C ALL
121VUAPU/FIRE AND OVHT/DET/LOOP B2WGL44
121VUAPU/FIRE AND OVHT/DET/LOOP A1WGL43
Subtask 31-32-00-740-078-A
B. On the CFDS MENU page, get access to the AVIONICS STATUS page AMM 31-32-00-869-002.
4. Fault Isolation
Subtask 31-32-00-810-064-A
A. If the test gives the maintenance message NO FDU APU DATA:
   (1) If the fault continues:
     (a) If the fault continues:
  • do a check and repair the wiring from CFDIU (1TW) to the FDU of the APU (13WG) from pins AA/2D, 2E to pins A/G, F , ASM 313206.
Subtask 31-32-00-740-079-A
B. Do the test given in Para. 3.B.