W DOC AIRBUS | TSM A320F

Loss of the Power Supply of the Side Windows


TASK 30-42-00-810-818-A
Loss of the Power Supply of the Side Windows


1. Possible Causes
  • WHC-2 [2DG2]
  • wiring
  • C/B-ANTI ICE/WINDOWS/R [4DG2]
2. Job Set-up Information
 A. Referenced Information
REFERENCE
DESIGNATION
TSM TASK 24-00-00-810-803-A
Circuit Breaker Tripped and/or C/B TRIPPED Warning
AMM 30-42-00-710-001
Operational Test of the Windshield Anti-Icing and Defogging
ASM 304202
AMM 30-42-34-000-001
Removal of the Window Heat Computer (WHC)
AMM 30-42-34-400-001
Installation of the Window Heat Computer (WHC)
3. Fault Confirmation
Subtask 30-42-00-710-084-A
A. Test
   (1) Do the operational test of the windshield anti-icing and defogging AMM 30-42-00-710-001.
4. Fault Isolation
Subtask 30-42-00-865-061-A
A. Table of the circuit breakers used in this procedure:
PANELDESIGNATIONFINLOCATION
** ON A/C ALL
122VUANTI ICE/WINDOWS/R4DG2W14
Subtask 30-42-00-810-067-A
B. If the test gives the maintenance message CHECK WINDOWS WHC 2 SUPPLY:
  • Do a check of the status of the right windows anti-ice circuit breaker (4DG2)
   (1) If the circuit breaker is closed:
  • Open the right windows anti-ice circuit breaker (4DG2).
  • Remove the WHC2 AMM 30-42-34-000-001.
  • Close the right windows anti-ice circuit breaker (4DG2).
  • Do a check for 115VAC at pin B/G of the WHC2 (2DG2) ASM 304202.
     (a) If there is 115VAC:
     (b) If there is no 115VAC:
  • Do a check for a ground signal at pin A/G of the WHC2 (2DG2).
       1 If there is no ground signal:
  • Repair the wiring between the pin A/G of WHC2 and the ground terminal ASM 304202.
       2 If there is a ground signal:
  • Do a check of the wiring between pin B/G of the WHC2 and the right windows anti-ice circuit breaker (4DG2) ASM 304202.
         a If there is no continuity:
  • Repair the above wiring.
         b If there is continuity:
  • Replace the C/B-ANTI ICE/WINDOWS/R [4DG2] .
   (2) If the circuit breaker is open:
     (a) If the fault continues:
  • Replace the C/B-ANTI ICE/WINDOWS/R [4DG2] .
     (b) If the fault continues:
Subtask 30-42-00-710-085-A
C. Do the operational test given in Para. 3.
[Rev.8 from Aug 2018] 2026.04.04 04:29:42 UTC