Fuel Temperature Shows XX, Right Inner Cell
TASK 28-42-00-810-839-A
Fuel Temperature Shows XX, Right Inner Cell
2. Job Set-up Information
A. Referenced Information
3. Fault Confirmation
Subtask 28-42-00-710-088-A ** ON A/C NOT FOR ALL
Subtask 28-42-00-810-088-A ** ON A/C NOT FOR ALL
[Rev.8 from Aug 2018]
2026.04.04 04:29:07 UTC
Fuel Temperature Shows XX, Right Inner Cell
WARNING:
OBEY THE FUEL SAFETY PROCEDURES.
1. Possible Causes2. Job Set-up Information
A. Referenced Information
| REFERENCE | DESIGNATION |
|---|---|
| TSM TASK 28-42-00-810-805-A | Fuel Quantity/Temperature Probe 22QT1(2), Left(Right) Wing Tank |
Subtask 28-42-00-710-088-A ** ON A/C NOT FOR ALL
A. On the ECAM CONTROL PANEL, push (in) the FUEL pushbutton switch (P/BSW).
(1) Examine the fuel temperatures on the FUEL system page.
(2) If the right inner cell fuel temperature shows correctly:
4. Fault Isolation(1) Examine the fuel temperatures on the FUEL system page.
(2) If the right inner cell fuel temperature shows correctly:
- maintenance steps are not necessary.
Subtask 28-42-00-810-088-A ** ON A/C NOT FOR ALL
A. If the right inner cell fuel temperature shows XX.
(1) Examine the Post Flight Report (PFR) for the LRUs:
(2) If the LRUs listed in Para. (1) are shown:
(1) Examine the Post Flight Report (PFR) for the LRUs:
(2) If the LRUs listed in Para. (1) are shown: