Fuel Pumps - Left Wing Tank Fuel Pump No. 1 System Failure (Standby Supply)
TASK 28-21-00-810-805-A
Fuel Pumps - Left Wing Tank Fuel Pump No. 1 System Failure (Standby Supply)
A. Fixtures, Tools, Test and Support Equipment
B. Referenced Information
3. Fault Confirmation
Subtask 28-21-00-710-054-A
Subtask 28-21-00-810-054-B
[Rev.8 from Aug 2018]
2026.04.04 04:28:34 UTC
Fuel Pumps - Left Wing Tank Fuel Pump No. 1 System Failure (Standby Supply)
WARNING:
OBEY THE FUEL SAFETY PROCEDURES.
WARNING:
WHEN YOU DO WORK ON THE FUEL SYSTEM WIRING, YOU MUST USE TEST EQUIPMENT THAT IS APPROVED (REFER TO INTERNATIONAL OR NATIONAL SPECIFICATIONS FOR INTRINSICALLY SAFE TEST EQUIPMENT: EN50020, UL913 OR EQUIVALENT). TEST EQUIPMENT THAT IS NOT APPROVED CAN CAUSE FIRE OR AN EXPLOSION.
1. Possible Causes- C/B-L WING TK/PUMP 1/STBY SPLY [11QA]
- CT-AC, 1 [42XU3]
- CNTOR-L WING TK STBY SPLY, PUMP 1 [53QA]
aircraft wiring (three phase electrical standby supply)
A. Fixtures, Tools, Test and Support Equipment
| REFERENCE | QTY | DESIGNATION |
|---|---|---|
| No specific | AR | MULTIMETER - STANDARD |
| REFERENCE | DESIGNATION |
|---|---|
| TSM TASK 28-21-00-810-801-A | Fuel Pumps - Left Wing Tank Fuel Pump No. 1 (Outer) 21QA System Malfunction |
| TSM TASK 28-21-00-810-807-A | Fuel Pumps - Left Wing Tank Fuel Pump No. 1 Contactor Control Failure (Normal Supply) |
| AMM 24-22-00-710-001 | Operational Test of the Generator Line Contactor (GLC-1) Opening in the Smoke Procedure |
| ASM 242202 | |
| AMM 24-22-17-000-001 | Removal of the AC Current Transformers |
| AMM 24-22-17-400-001 | Installation of the AC Current Transformers |
| ASM 282101 |
Subtask 28-21-00-710-054-A
A. Test
(1) Do the Operational Test of the Generator Line Contactor (GLC-1) Opening in the Smoke Procedure AMM 24-22-00-710-001.
(2) If a low fuel pressure indiction is shown when the left wing tank fuel pump No. 1 is supplied from:
(a) The normal supply (AC BUS 1 and through the contactor-17QA), do (Ref. TSM TASK 28-21-00-810-801) and (Ref. TSM TASK 28-21-00-810-807).
(b) The standby supply (direct from the Generator No. 1 and through the contactor-53QA), do Para. 4.A.
4. Fault Isolation(1) Do the Operational Test of the Generator Line Contactor (GLC-1) Opening in the Smoke Procedure AMM 24-22-00-710-001.
(2) If a low fuel pressure indiction is shown when the left wing tank fuel pump No. 1 is supplied from:
(a) The normal supply (AC BUS 1 and through the contactor-17QA), do (Ref. TSM TASK 28-21-00-810-801) and (Ref. TSM TASK 28-21-00-810-807).
(b) The standby supply (direct from the Generator No. 1 and through the contactor-53QA), do Para. 4.A.
Subtask 28-21-00-810-054-B
A. Procedure
(1) Do a check of ASM 282101 and replace, if necessary:
aircraft wiring (three phase electrical standby supply) ASM 242202 and ASM 282101 between:
(4) Do the test given in Para. 3.A.
(1) Do a check of ASM 282101 and replace, if necessary:
- the C/B- C/B-L WING TK/PUMP 1/STBY SPLY [11QA]
- the CT-AC, 1 [42XU3] AMM 24-22-17-000-001 and AMM 24-22-17-400-001
- the CNTOR-L WING TK STBY SPLY, PUMP 1 [53QA] .
- the contactor GLC-1 (9XU1) (Gen 1 connected terminals D, E and F) and the C/B-L WING TK/PUMP 1/STBY SPLY (11QA)
NOTE: Each phase of the wiring between these two units goes through a different toroidal transformer of the CT-AC, 1 (42XU3). There is no direct electrical connection.
- the C/B-L WING TK/PUMP 1/STBY SPLY (11QA) and the CNTOR-L WING TK STBY SPLY, PUMP 1 (53QA)
- CNTOR-L WING TK STBY SPLY, PUMP 1 (53QA) and the PUMP-FUEL No. 1, L WING TK free connector 21QA-A.
(4) Do the test given in Para. 3.A.