Loss of the SEC 3 BUS Signal for the FCDC 2


TASK 27-95-00-810-813-A
Loss of the SEC 3 BUS Signal for the FCDC 2


1. Possible Causes
  • FCDC-2 [3CE2]
  • wiring of the DGI 3/2 signal from the FCDC 2 (3CE2) to the first terminal block
  • wiring of the DGI 3/4 signal from the FCDC 2 (3CE2) to the first terminal block
2. Job Set-up Information
 A. Referenced Information
REFERENCE
DESIGNATION
ASM 279255
AMM 27-95-34-000-001
Removal of the FCDC
AMM 27-95-34-400-001
Installation of the FCDC
AMM 27-96-00-740-001
BITE Test of the EFCS (Ground Scanning)
3. Fault Confirmation
Subtask 27-95-00-740-068-A
A. Test
   (1) Do the BITE test of the EFCS (ground scanning) AMM 27-96-00-740-001.
4. Fault Isolation
Subtask 27-95-00-810-059-A
A. If the BITE test gives the maintenance message:
FCDC2 OR BUS FROM SEC3 COM
or
FCDC2 OR BUS FROM SEC3 MON
   (1) If the fault continues:
  • do a check and repair the wiring of the DGI 3/2 signal from the FCDC 2 (3CE2) to the first terminal block ASM 279255 if the maintenance message is FCDC2 OR BUS FROM SEC3 COM
    or
  • do a check and repair the wiring of the DGI 3/4 signal from the FCDC 2 (3CE2) to the first terminal block ASM 279255 if the maintenance message is FCDC2 OR BUS FROM SEC3 MON.
Subtask 27-95-00-740-069-A
B. Do the test given in Para. 3.