Loss of the Pitch Signal on the F/O Side Stick for the SEC 2 (New-Generation Side-Stick Unit)
TASK 27-94-00-810-913-A
Loss of the Pitch Signal on the F/O Side Stick for the SEC 2 (New-Generation Side-Stick Unit)
1. Possible Causes
2. Job Set-up Information
A. Referenced Information
3. Fault Confirmation
Subtask 27-94-00-700-119-A
Subtask 27-94-00-810-158-A
[Rev.8 from Aug 2018]
2026.04.04 04:28:21 UTC
Loss of the Pitch Signal on the F/O Side Stick for the SEC 2 (New-Generation Side-Stick Unit)
1. Possible Causes
2. Job Set-up Information
A. Referenced Information
| REFERENCE | DESIGNATION |
|---|---|
| ASM 279215 | |
| AMM 27-92-41-000-802 | Removal of the New-Generation Side-Stick Unit |
| AMM 27-92-41-400-802 | Installation of the New-Generation Side-Stick Unit |
| AMM 27-94-34-000-001 | Removal of the SEC |
| AMM 27-94-34-400-001 | Installation of the SEC |
| AMM 27-96-00-710-020 | Operational Test of the Side Stick Assembly (Activation for the BITE Test) |
| AMM 27-96-00-740-001 | BITE Test of the EFCS (Ground Scanning) |
Subtask 27-94-00-700-119-A
A. Test
(1) Do the operational test of the side-stick unit (activation for the BITE test) AMM 27-96-00-710-020.
(2) Do the BITE test of the EFCS (Ground Scanning) AMM 27-96-00-740-001.
4. Fault Isolation(1) Do the operational test of the side-stick unit (activation for the BITE test) AMM 27-96-00-710-020.
(2) Do the BITE test of the EFCS (Ground Scanning) AMM 27-96-00-740-001.
Subtask 27-94-00-810-158-A
A. If the BITE test gives the maintenance message:
SEC2 OR INPUT OF F/O PITCH CTL SSTU 4CE4
Subtask 27-94-00-700-120-A SEC2 OR INPUT OF F/O PITCH CTL SSTU 4CE4
- replace the SSU-F/O [100CE2] , AMM 27-92-41-000-802 and AMM 27-92-41-400-802.
- replace the SEC-2 [1CE2] , AMM 27-94-34-000-001 and AMM 27-94-34-400-001.
- do a check and repair the
wiring from the SEC 2 (1CE2) to the SSU (100CE2) , ASM 279215.
B. Do the operational test and the BITE test given in Para. 3.