SEC 1 Fault without any associated maintenance message
TASK 27-94-00-810-901-A
SEC 1 Fault without any associated maintenance message
1. Possible Causes
A. Referenced Information
3. Fault Confirmation
Subtask 27-94-00-740-173-A 4. Fault Isolation
Subtask 27-94-00-810-146-A
[Rev.8 from Aug 2018]
2026.04.04 04:39:10 UTC
SEC 1 Fault without any associated maintenance message
1. Possible Causes
- RELAY-SEC 1 ANN SPLY [41CE1]
- wiring of the RLY SEC FAULT signal from the relay to the SEC
- SEC-1 [1CE1]
wiring of the DSI 4/3 (SEC 1 FAILED) signals
A. Referenced Information
| REFERENCE | DESIGNATION |
|---|---|
| ASM 279205 | |
| AIPC 27920803 | |
| AMM 27-94-00-710-002 | Operational Test of the Spoiler Elevator Computer 1 (SEC 1) |
| AMM 27-94-34-000-001 | Removal of the SEC |
| AMM 27-94-34-400-001 | Installation of the SEC |
| ASM 279504 | |
| ASM 279505 | |
| AMM 27-96-00-740-001 | BITE Test of the EFCS (Ground Scanning) |
Subtask 27-94-00-740-173-A 4. Fault Isolation
Subtask 27-94-00-810-146-A
A. If the test confirms the fault:
(a) Remove the SEC1 AMM 27-94-34-000-001.
(b) At the SEC1 receptacle, do a check of the resistance between pin AB/12K and pin AE/12A ASM 279205.
1 If the resistance is less than 280 ohms:
a Remove the RELAY-SEC 1 ANN SPLY [41CE1] AIPC 27920803.
b Do a check of the resistance of the relay between pin X1 and X2.
a Remove the relay (41CE1).
b Do a check of the resistance of the relay between pin X1 and X2.
a Remove the RELAY-SEC 1 ANN SPLY (41CE1) AIPC 27920803.
wiring of the DSI 4/3 (SEC 1 FAILED) signals from the FCDC1 (3CE1) and the FCDC2 (3CE2) to the RELAY-SEC 1 ANN SPLY (41CE1) ASM 279504 and ASM 279505.
c Install the SEC 1 AMM 27-94-34-400-001.
Subtask 27-94-00-740-174-A - do the operational test of the SEC1 AMM 27-94-00-710-002 to make sure that the SEC1 servoes its associated surfaces.
(a) Remove the SEC1 AMM 27-94-34-000-001.
(b) At the SEC1 receptacle, do a check of the resistance between pin AB/12K and pin AE/12A ASM 279205.
1 If the resistance is less than 280 ohms:
a Remove the RELAY-SEC 1 ANN SPLY [41CE1] AIPC 27920803.
b Do a check of the resistance of the relay between pin X1 and X2.
- If the resistance is less than 280 Ohms:
. replace the RELAY-SEC 1 ANN SPLY [41CE1] AIPC 27920803
. install the SEC1 AMM 27-94-34-400-001. - If the resistance is between 280 and 400 ohms:
. do a check and repair the wiring of the RLY SEC FAULT signal from the relay to the SEC ASM 279205
. install the relay
. replace the SEC-1 [1CE1] AMM 27-94-34-400-001.
a Remove the relay (41CE1).
b Do a check of the resistance of the relay between pin X1 and X2.
- If the resistance is more than 400 ohms:
. replace the RELAY-SEC 1 ANN SPLY [41CE1] AIPC 27920803
. install the SEC 1 AMM 27-94-34-400-001. - If the resistance is between 280 and 400 ohms:
. do a check and repair the wiring of the RLY SEC FAULT signal from the relay to the SEC ASM 279205
. install the relay
. install the SEC 1 AMM 27-94-34-400-001.
a Remove the RELAY-SEC 1 ANN SPLY (41CE1) AIPC 27920803.
- if the warning SEC1 stays, install the relay AIPC 27920803 and see Para. b_.
- if the warning SEC1 goes off, replace the RELAY-SEC 1 ANN SPLY [41CE1] AIPC 27920803
- install the SEC 1 AMM 27-94-34-400-001.
c Install the SEC 1 AMM 27-94-34-400-001.
B. Do the test given in Para. 3.