Loss of the ELAC 2 COM BUS 1 Signal for the SEC 2
TASK 27-94-00-810-898-A
Loss of the ELAC 2 COM BUS 1 Signal for the SEC 2
1. Possible Causes
A. Referenced Information
3. Fault Confirmation
Subtask 27-94-00-740-168-A 4. Fault Isolation
Subtask 27-94-00-810-138-A
[Rev.8 from Aug 2018]
2026.04.04 04:28:20 UTC
Loss of the ELAC 2 COM BUS 1 Signal for the SEC 2
1. Possible Causes
- SEC-2 [1CE2]
wiring of the DGI 09 signal from the SEC2 (1CE2) COM part and MON part to the first terminal block wiring of the DSI 21 signal from the SEC2 (1CE2) COM part and MON part to the first terminal block
A. Referenced Information
| REFERENCE | DESIGNATION |
|---|---|
| TSM TASK 31-32-00-810-934-A | Failure of the Digital Links |
| ESPM 2052220 | |
| ASM 279249 | |
| ASM 279252 | |
| AMM 27-94-34-000-001 | Removal of the SEC |
| AMM 27-94-34-400-001 | Installation of the SEC |
| AMM 27-96-00-740-001 | BITE Test of the EFCS (Ground Scanning) |
Subtask 27-94-00-740-168-A 4. Fault Isolation
Subtask 27-94-00-810-138-A
A. If the test gives the maintenance message:
SEC2 OR BUS1 FROM ELAC2 COM
(a) Do a check of thewiring of the DGI 09 signal from the SEC2 (1CE2) COM part and MON part to the first terminal block ASM 279252.
wiring of the DSI 21 signal from the SEC2 (1CE2) COM part and MON part to the first terminal block ASM 279249.
Subtask 27-94-00-740-169-A SEC2 OR BUS1 FROM ELAC2 COM
- replace the SEC-2 [1CE2] AMM 27-94-34-000-001 and AMM 27-94-34-400-001.
- do the trouble shooting procedure (Ref. TSM TASK 31-32-00-810-934) related to the DGO 01 digital output signal of the ELAC2 ASM 279252.
- at the ELAC2 receptacle, do a check of the insulation of the wiring of the DGO 01 signal ASM 279252 ESPM 2052220.
(a) Do a check of the
- if there is continuity, see Para. (b)
- if there is no continuity, repair the above wiring.
B. Do the test given in Para. 3.