Loss of the FCDC 2 BUS 6 Signal for the SEC 2


TASK 27-94-00-810-882-A
Loss of the FCDC 2 BUS 6 Signal for the SEC 2


1. Possible Causes
  • SEC-2 [1CE2]
  • wiring of the DGI 10 signal from the SEC2 (1CE2) to the first terminal block
2. Job Set-up Information
 A. Referenced Information
REFERENCE
DESIGNATION
AMM 27-94-34-000-001
Removal of the SEC
AMM 27-94-34-400-001
Installation of the SEC
ASM 279503
AMM 27-96-00-740-001
BITE Test of the EFCS (Ground Scanning)
3. Fault Confirmation
Subtask 27-94-00-740-132-A
A. Test
   (1) Do the BITE test of the EFCS (ground scanning) AMM 27-96-00-740-001.
4. Fault Isolation
Subtask 27-94-00-810-119-A
A. If the BITE test gives the maintenance message:
SEC2 MON OR BUS6 FROM FCDC2
   (1) If the fault continues:
  • do a check and repair the wiring of the DGI 10 signal from the SEC2 (1CE2) to the first terminal block ASM 279503.
Subtask 27-94-00-740-133-A
B. Do the test given in Para. 3.