Loss of the BUS 1 Signal for the SEC 3
TASK 27-94-00-810-877-A
Loss of the BUS 1 Signal for the SEC 3
1. Possible Causes
A. Referenced Information
3. Fault Confirmation
Subtask 27-94-00-740-122-A 4. Fault Isolation
Subtask 27-94-00-810-114-A
[Rev.8 from Aug 2018]
2026.04.04 04:28:18 UTC
Loss of the BUS 1 Signal for the SEC 3
1. Possible Causes
- SEC-3 [1CE3]
wiring of the DGO1 signal from the SEC 3 (1CE3) COM part to the first terminal block wiring of the DGO1 signal from the SEC 3 (1CE3) MON part to the first terminal block
A. Referenced Information
| REFERENCE | DESIGNATION |
|---|---|
| TSM TASK 31-32-00-810-934-A | Failure of the Digital Links |
| ASM 279255 | |
| AMM 27-94-34-000-001 | Removal of the SEC |
| AMM 27-94-34-400-001 | Installation of the SEC |
| AMM 27-96-00-740-001 | BITE Test of the EFCS (Ground Scanning) |
Subtask 27-94-00-740-122-A 4. Fault Isolation
Subtask 27-94-00-810-114-A
A. If the BITE test gives the maintenance message:
SEC3 COM BUS1
or
SEC3 MON BUS1
Subtask 27-94-00-740-123-A SEC3 COM BUS1
or
SEC3 MON BUS1
- replace the SEC-3 [1CE3] AMM 27-94-34-000-001 and AMM 27-94-34-400-001.
- do the trouble shooting procedure (Ref. TSM TASK 31-32-00-810-934) related to the DGO digital output signal of the SEC 3 ASM 279255.
- do a check and repair the
wiring of the DGO1 signal from the SEC 3 (1CE3) COM part to the first terminal block if the maintenance message is SEC 3 COM BUS 1 ASM 279255
or - do a check and repair the
wiring of the DGO1 signal from the SEC 3 (1CE3) MON part to the first terminal block if the maintenance message is SEC 3 MOM BUS 1 ASM 279255.
B. Do the test given in Para. 3.