Loss of the BUS 1 Signal for the SEC 1
TASK 27-94-00-810-876-A
Loss of the BUS 1 Signal for the SEC 1
1. Possible Causes
A. Referenced Information
3. Fault Confirmation
Subtask 27-94-00-740-120-A 4. Fault Isolation
Subtask 27-94-00-810-113-A
[Rev.8 from Aug 2018]
2026.04.04 04:28:18 UTC
Loss of the BUS 1 Signal for the SEC 1
1. Possible Causes
- SEC-1 [1CE1]
wiring of the DGO 01 signal from the SEC 1 (1CE1) COM part to the first terminal block wiring of the DGO 01 signal from the SEC 1 (1CE1) MON part to the first terminal block
A. Referenced Information
| REFERENCE | DESIGNATION |
|---|---|
| TSM TASK 31-32-00-810-934-A | Failure of the Digital Links |
| ASM 279253 | |
| AMM 27-94-34-000-001 | Removal of the SEC |
| AMM 27-94-34-400-001 | Installation of the SEC |
| AMM 27-96-00-740-001 | BITE Test of the EFCS (Ground Scanning) |
Subtask 27-94-00-740-120-A 4. Fault Isolation
Subtask 27-94-00-810-113-A
A. If the BITE test gives the maintenance message:
SEC1 COM BUS1
or
SEC1 MON BUS1
Subtask 27-94-00-740-121-A SEC1 COM BUS1
or
SEC1 MON BUS1
- replace the SEC-1 [1CE1] AMM 27-94-34-000-001 and AMM 27-94-34-400-001.
- do the trouble shooting procedure (Ref. TSM TASK 31-32-00-810-934) related to the DGO 01 digital output signal of the SEC 1 ASM 279253.
- do a check and repair the
wiring of the DGO 01 signal from the SEC 1 (1CE1) COM part to the first terminal block if the maintenance message is SEC 1 COM BUS 1 ASM 279253
or - do a check and repair the
wiring of the DGO 01 signal from the SEC 1 (1CE1) MON part to the first terminal block if the maintenance message is SEC 1 MOM BUS 1 ASM 279253.
B. Do the test given in Para. 3.