Loss of the BUS 3 Signal for the SEC 1
TASK 27-94-00-810-864-A
Loss of the BUS 3 Signal for the SEC 1
1. Possible Causes
A. Referenced Information
3. Fault Confirmation
Subtask 27-94-00-740-112-A 4. Fault Isolation
Subtask 27-94-00-810-109-A
[Rev.8 from Aug 2018]
2026.04.04 04:28:16 UTC
Loss of the BUS 3 Signal for the SEC 1
1. Possible Causes
- SEC-1 [1CE1]
wiring of the DG03 signal from the SEC1 (1CE1) MON part to COM part wiring of the DG03 signal from the SEC1 (1CE1) COM part to MON part
A. Referenced Information
| REFERENCE | DESIGNATION |
|---|---|
| ASM 279253 | |
| AMM 27-94-34-000-001 | Removal of the SEC |
| AMM 27-94-34-400-001 | Installation of the SEC |
| AMM 27-96-00-740-001 | BITE Test of the EFCS (Ground Scanning) |
Subtask 27-94-00-740-112-A 4. Fault Isolation
Subtask 27-94-00-810-109-A
A. If the BITE test gives the maintenance message:
SEC1 MON BUS3
or
SEC1 COM BUS3
Subtask 27-94-00-740-113-A SEC1 MON BUS3
or
SEC1 COM BUS3
- replace the SEC-1 [1CE1] AMM 27-94-34-000-001 and AMM 27-94-34-400-001.
- do a check and repair the
wiring of the DG03 signal from the SEC1 (1CE1) MON part to COM part if the maintenance message is SEC1 MON BUS3 ASM 279253
or - do a check and repair the
wiring of the DG03 signal from the SEC1 (1CE1) COM part to MON part if the maintenance message is SEC1 COM BUS3 ASM 279253.
B. Do the test given in Para. 3.