Loss of the IR 3 Bus 2 for the SEC 3


TASK 27-94-00-810-853-A
Loss of the IR 3 Bus 2 for the SEC 3


1. Possible Causes
  • SEC-3 [1CE3]
  • wiring of the DGI-02 signal from the SEC 3 (1CE3) to the first terminal block
2. Job Set-up Information
 A. Referenced Information
REFERENCE
DESIGNATION
ASM 279255
AMM 27-94-34-000-001
Removal of the SEC
AMM 27-94-34-400-001
Installation of the SEC
AMM 27-96-00-740-001
BITE Test of the EFCS (Ground Scanning)
3. Fault Confirmation
Subtask 27-94-00-740-098-A
A. Test
   (1) Do the BITE test of the EFCS (ground scanning) AMM 27-96-00-740-001.
4. Fault Isolation
Subtask 27-94-00-810-102-B
A. If the BITE test gives the maintenance message:
SEC3 OR BUS2 FROM IR3
   (1) If the fault continues:
  • do a check and repair the wiring of the DGI-02 signal from the SEC 3 (1CE3) to the first terminal block, COM and MON parts ASM 279255.
Subtask 27-94-00-740-099-A
B. Do the test given in Para. 3.
[Rev.8 from Aug 2018] 2026.04.04 04:28:15 UTC