Loss of the IR 2 Bus 2 for the SEC 2


TASK 27-94-00-810-850-A
Loss of the IR 2 Bus 2 for the SEC 2


1. Possible Causes
  • SEC-2 [1CE2]
  • wiring of the DGI-02 signal from the SEC 2 (1CE2) to the first terminal block
2. Job Set-up Information
 A. Referenced Information
REFERENCE
DESIGNATION
ASM 279254
AMM 27-94-34-000-001
Removal of the SEC
AMM 27-94-34-400-001
Installation of the SEC
AMM 27-96-00-740-001
BITE Test of the EFCS (Ground Scanning)
3. Fault Confirmation
Subtask 27-94-00-740-092-A
A. Test
   (1) Do the BITE test of the EFCS (ground scanning) AMM 27-96-00-740-001.
4. Fault Isolation
Subtask 27-94-00-810-099-B
A. If the BITE test gives the maintenance message:
SEC2 OR BUS2 FROM IR2
   (1) If the fault continues:
  • do a check and repair the wiring of the DGI-02 signal from the SEC 2 (1CE2) to the first terminal block, COM and MON parts ASM 279254.
Subtask 27-94-00-740-093-A
B. Do the test given in Para. 3.