Loss of the Yellow Hydraulic Pressure Switch Signal for the SEC 3
TASK 27-94-00-810-835-A
Loss of the Yellow Hydraulic Pressure Switch Signal for the SEC 3
1. Possible Causes
A. Referenced Information
3. Fault Confirmation
Subtask 27-94-00-860-066-A Subtask 27-94-00-865-061-A
Subtask 27-94-00-810-084-B
Subtask 27-94-00-860-067-A
[Rev.8 from Aug 2018]
2026.04.04 04:28:14 UTC
Loss of the Yellow Hydraulic Pressure Switch Signal for the SEC 3
1. Possible Causes
- SEC-3 [1CE3]
wiring of the LOW YELLOW PRESS signal from the SEC 3 (1CE3) COM and MON parts to the first terminal block
A. Referenced Information
| REFERENCE | DESIGNATION |
|---|---|
| ASM 279227 | |
| AMM 27-94-34-000-001 | Removal of the SEC |
| AMM 27-94-34-400-001 | Installation of the SEC |
| AMM 27-96-00-740-001 | BITE Test of the EFCS (Ground Scanning) |
| AMM 29-10-00-863-002 | Pressurize the Yellow Hydraulic System with a Hydraulic Ground Power-Cart |
| AMM 29-10-00-864-002 | Depressurize the Yellow Hydraulic System |
Subtask 27-94-00-860-066-A Subtask 27-94-00-865-061-A
B. Table of the circuit breakers used in this procedure:
Subtask 27-94-00-740-074-A 4. Fault Isolation| PANEL | DESIGNATION | FIN | LOCATION |
|---|---|---|---|
| ** ON A/C ALL | |||
| 49VU | FLIGHT CONTROLS/FCDC1/SPLY | 20CE1 | B10 |
| 121VU | FLIGHT CONTROLS/FCDC2/SPLY | 20CE2 | Q20 |
Subtask 27-94-00-810-084-B
A. If the BITE test gives the maintenance message:
SEC3 OR WIRING FROM Y HYD PRESS SW2
Subtask 27-94-00-740-075-A SEC3 OR WIRING FROM Y HYD PRESS SW2
- replace the SEC-3 [1CE3] , AMM 27-94-34-000-001 and AMM 27-94-34-400-001.
- open and close the circuit breakers 20CE1 and 20CE2.
- do a check and repair the
wiring of the LOW YELLOW PRESS signal from the SEC 3 (1CE3) COM and MON parts to the first terminal block , ASM 279227. - open and close the circuit breakers 20CE1 and 20CE2.
B. Do the test given in Para. 3.
5. Close-upSubtask 27-94-00-860-067-A