Loss of the LGCIU 1 Discrete Inputs for the ELAC
TASK 27-93-00-810-921-A
Loss of the LGCIU 1 Discrete Inputs for the ELAC
1. Possible Causes
A. Referenced Information
3. Fault Confirmation
Subtask 27-93-00-740-162-A 4. Fault Isolation
Subtask 27-93-00-865-051-A
[Rev.8 from Aug 2018]
2026.04.04 04:28:06 UTC
Loss of the LGCIU 1 Discrete Inputs for the ELAC
1. Possible Causes
- PROX SNSR-R L/G EXT, SYS 1 [20GA]
- PROX SNSR-L L/G EXT, SYS 1 [21GA]
- PROX SNSR-NLG EXT, SYS 1 [24GA]
- ELAC-2 [2CE2]
- LGCIU-1 [5GA1]
wiring from the ELAC 2 (2CE2) to the LGCIU 1 (5GA1) - ELAC-1 [2CE1]
wiring from the ELAC 1 (2CE1) to the LGCIU 1 (5GA1)
A. Referenced Information
| REFERENCE | DESIGNATION |
|---|---|
| ASM 279243 | |
| AMM 27-93-34-000-001 | Removal of the ELAC |
| AMM 27-93-34-400-001 | Installation of the ELAC |
| AMM 27-96-00-740-001 | BITE Test of the EFCS (Ground Scanning) |
| AMM 32-31-71-000-001 | Removal of the LGCIU |
| AMM 32-31-71-400-001 | Installation of the LGCIU |
| AMM 32-31-73-000-001 | Removal of the MLG Proximity-Sensors |
| AMM 32-31-73-000-005 | Removal of the NLG Proximity-Sensors |
| AMM 32-31-73-400-001 | Installation of the MLG Proximity-Sensors |
| AMM 32-31-73-400-005 | Installation of the NLG Proximity-Sensors |
Subtask 27-93-00-740-162-A 4. Fault Isolation
Subtask 27-93-00-865-051-A
A. Table of the circuit breakers used in this procedure:
Subtask 27-93-00-810-219-A | PANEL | DESIGNATION | FIN | LOCATION |
|---|---|---|---|
| ** ON A/C ALL | |||
| 49VU | FLIGHT CONTROLS/ELAC1/NORM/SPLY | 15CE1 | B11 |
| 105VU | FLIGHT CONTROLS/ELAC2/STBY SPLY | 16CE2 | A02 |
| 105VU | FLT CTL/ELAC1/STBY SPLY | 16CE1 | A01 |
| 121VU | FLIGHT CONTROLS/ELAC2/NORM/SPLY | 15CE2 | R20 |
B. If the test doesn't confirm the fault or if the maintenance message CHECK LGCIU1 DISC INPUTS was shown after landing gear free-fall extension:
Subtask 27-93-00-810-155-A - no maintenance action is necessary.
C. If the BITE test gives the maintenance message:
CHECK LGCIU1 DISC INPUTS
(5) Open the circuit breaker (15CE2) on the panel 121VU and the circuit breaker (16CE2) on the panel 105VU and do the test given in Para. 3.
(6) Close the circuit breakers (15CE2) and (16CE2).
(a) If the message is shown only when the circuit breakers (15CE1) and (16CE1) are open:
Subtask 27-93-00-740-163-A CHECK LGCIU1 DISC INPUTS
- replace the PROX SNSR-R L/G EXT, SYS 1 [20GA] AMM 32-31-73-000-001 and AMM 32-31-73-400-001.
- replace the PROX SNSR-L L/G EXT, SYS 1 [21GA] AMM 32-31-73-000-001 AMM 32-31-73-400-001.
- replace the PROX SNSR-NLG EXT, SYS 1 [24GA] AMM 32-31-73-000-005 AMM 32-31-73-400-005.
- open the circuit breaker (15CE1) on the panel 49VU and the circuit breaker (16CE1) on the panel 105VU and do the test given in Para. 3.
(5) Open the circuit breaker (15CE2) on the panel 121VU and the circuit breaker (16CE2) on the panel 105VU and do the test given in Para. 3.
(6) Close the circuit breakers (15CE2) and (16CE2).
(a) If the message is shown only when the circuit breakers (15CE1) and (16CE1) are open:
- replace the ELAC-2 [2CE2] AMM 27-93-34-000-001 and AMM 27-93-34-400-001.
- replace the LGCIU-1 [5GA1] AMM 32-31-71-000-001 and AMM 32-31-71-400-001.
- do a check and repair the
wiring from the ELAC 2 (2CE2) to the LGCIU 1 (5GA1) ASM 279243.
- replace the ELAC-1 [2CE1] AMM 27-93-34-000-001 and AMM 27-93-34-400-001.
- replace the LGCIU-1 [5GA1] AMM 32-31-71-000-001 and AMM 32-31-71-400-001.
- do a check and repair the
wiring from the ELAC 1 (2CE1) to the LGCIU 1 (5GA1) ASM 279243.
- replace the LGCIU-1 [5GA1] AMM 32-31-71-000-001 and AMM 32-31-71-400-001.
D. Do the test given in Para. 3.