Loss of the SEC 1 BUS Signal for the ELAC 2
TASK 27-93-00-810-912-A
Loss of the SEC 1 BUS Signal for the ELAC 2
1. Possible Causes
A. Referenced Information
3. Fault Confirmation
Subtask 27-93-00-740-152-A 4. Fault Isolation
Subtask 27-93-00-810-150-A
[Rev.8 from Aug 2018]
2026.04.04 04:28:05 UTC
Loss of the SEC 1 BUS Signal for the ELAC 2
1. Possible Causes
- ELAC-2 [2CE2]
wiring of the DGI 14 signal from the ELAC 2 (2CE2) to the first terminal block
A. Referenced Information
| REFERENCE | DESIGNATION |
|---|---|
| ASM 279253 | |
| AMM 27-93-34-000-001 | Removal of the ELAC |
| AMM 27-93-34-400-001 | Installation of the ELAC |
| AMM 27-96-00-740-001 | BITE Test of the EFCS (Ground Scanning) |
Subtask 27-93-00-740-152-A 4. Fault Isolation
Subtask 27-93-00-810-150-A
A. If the BITE test gives the maintenance message:
ELAC2 OR BUS FROM SEC1
(1) Replace the ELAC-2 [2CE2] AMM 27-93-34-000-001 and AMM 27-93-34-400-001.
(2) If the fault continues:
Subtask 27-93-00-740-153-A ELAC2 OR BUS FROM SEC1
(1) Replace the ELAC-2 [2CE2] AMM 27-93-34-000-001 and AMM 27-93-34-400-001.
(2) If the fault continues:
- Do a check and repair the
wiring of the DGI 14 signal from the ELAC 2 (2CE2) to the first terminal block ASM 279253.
B. Do the test given in Para. 3.